Programming 107
The analog output level will correspond to the output voltage level of the Drive. 100% will be equivalent to either 200Vac or
400Vac depending on the input voltage rating of the Drive.
Function: DC Bus Voltage
Setting: 7
The analog output level will correspond to the voltage level of the Drive’s DC Bus. 100% will correspond to 400Vdc for the
240Vac input Drive and 800Vdc for the 480Vac input Drive.
Function: Output kWatts
Setting: 8
The analog output level will correspond to an internally calculated output power level based on the measured output current
and output voltage. 100% will correspond to the kilowatt rating of the Drive as determined by o2-04.
Function: Torque Reference
Setting: 9
The analog output level will correspond to the torque reference. 100% will correspond to the Drive’s rated power as
determined by o2-04.
Function: Terminal A1 Level
Setting: 15
The analog output level will correspond to the analog input to the Drive’s A1 terminal. 100% will be equivalent to 10Vdc.
Function: Terminal A2 Level
Setting: 16
The analog output level will correspond to the analog input to the Drive’s A2 terminal. 100% will be equivalent to 10Vdc or
20mA.
Function: Terminal A3 Level
Setting: 17
The analog output level will correspond to the analog input to the Drive’s A3 terminal. 100% will be equivalent to 10Vdc.
Function: Motor SEC Current
Setting: 18
The analog output level will correspond to the calculated secondary (torque producing) current. 100% will be equivalent to
motor’s full load secondary current as calculated by:
Function: Mot EXC Current
Setting: 19
The analog output level will correspond to the calculated motor excitation (magnetizing) current. 100% will be equivalent to
motor rated magnetizing current.
I sec =
√
Ι
Nameplate
2
- I
no load
2
=
√
(
E2-01)
2
- (E2-03)
2