Programming 172
H1-03
Multi-Function Digital Input
Terminal S5 Function
Selection
Terminal S5 Sel
15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09, regardless of run
command status.
16: Motor 2 Selection
Closed = Motor 2 (E3-
, E4-
)
Open = Motor 1 (A1-02, E1-
, E2-
)
17: Fast-Stop N.C.
Closed = Normal operation
Open = Drive decelerates using C1-09, regardless of run
command status.
18: Timer Function
Input for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with the multi-function digital output
function H2-
= 12 “timer output”.
19: PID Disable
Closed = Turns off the PID controller.
1A: Accel / Decel Time Selection 2
Based on status of Accel/Decel Time Selection 1 and 2.
1B: Program Lockout
Closed = All parameter settings can be changed.
Open = Only using monitor U1-01 can be changed.
1C: Trim Control Increase
Closed = Increase frequency reference by value in d4-02.
Open = Return to normal frequency reference.
Not effective when Preset References are selected (Multi-step
speed digital inputs are closed). Must be used in conjunction
with Trim Ctrl Decrease.
1D: Trim Control Decrease
Closed = Decrease frequency reference by value in d4-02
Open = Return to normal frequency reference.
Not effective when Preset References are selected (Multi-step
speed digital inputs are closed). Must be used in conjunction
with Trim Ctrl Increase.
1E: Reference Sample Hold
Analog frequency reference is sampled then held at time of
input closure.
20: External Fault, Normally Open, Always Detected, Ramp To
Stop
21: External Fault, Normally Closed, Always Detected, Ramp To
Stop
22: External Fault, Normally Open, During Run, Ramp To Stop
23: External Fault, Normally Closed, During Run, Ramp To Stop
24: External Fault, Normally Open, Always Detected, Coast To
Stop
25: External Fault, Normally Closed, Always Detected, Coast To
Stop
26: External Fault, Normally Open, During Run, Coast To Stop
27: External Fault, Normally Closed, During Run, Coast To Stop
28: External Fault, Normally Open, Always Detected, Fast-Stop
29: External Fault, Normally Closed, Always Detected, Fast-Stop
2A:External Fault, Normally Open, During Run, Fast-Stop
2B:External Fault, Normally Closed, During Run, Fast-Stop
2C:External Fault, Normally Open, Always Detected, Alarm Only
2D:External Fault, Normally Closed, Always Detected, Alarm
Only
2E: External Fault, Normally Open, During Run, Alarm Only
2F: External Fault, Normally Closed, During Run, Alarm Only
(Continued on following page).
0 to 78
3:
2-wire
0:
3-wire
A
A
A
A
H1-04
Multi-Function Digital Input
Terminal S6 Function
Selection
Terminal S6 Sel
0 to 78
4:
2-wire
3:
3-wire
A
A
A
A
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Control Method
V/F
V/F
w/
PG
Open
Loop
Vector
Flux
Vector