iv
Drive Output Specifications
The standard Drive specifications are listed in the following tables.
208-240Vac
Table i.2 208-240Vac Drive Specifications
208-240Vac
208-230Vac
Model Number CIMR-F7U
20P4
20P7 21P5
22P2 23P7 25P5 27P5 2011 2015 2018 2022 2030 2037 2045 2055
2075
2090
2110
Rated output
capacity
(kVA)
1.2
1.6
2.7
3.7
5.7
8.8
12.0 17.0 22.0 27.0 32.0 44.0 55.0
69.0 82.0
110.0
130.0
N/A
Horsepower
*2
0.5/0.75
2
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
Rated output
current
(A)
3.2
4.2
7.0
9.6
15.2 23.0 31.0 45.0 58.0
71
85.0 115.0 145.0 180.0 215
283.0
346.0
Overload capacity
*3
(% of rated output
current for 60 sec.)
150
Current limit (% of
rated output current)
150
Carrier frequency
*4
2kHz
Maximum output
frequency
300.0Hz
Rated output
capacity
(kVA)
1.4
1.8
3.0
4.1
6.4
8.8
12.0 18.0 23.0 29.0 34.0 44.0 62.0
73.0 82.0
120.0
140.0 160.0
Horsepower
*2
0.5/0.75
1
2
3
5
7.5
10
15
20
25
30
40
50/60
75
75
100/125 150
150
Rated output
current
(A)
3.6
4.6
7.8
10.8 16.8 23.0 31.0 46.2 59.4 74.8 88.0 115.0 162.0 192.0 215
312.0
360.0 415.0
Overload capacity
*3
(% of rated output
current for 60 sec.)
107
107
108
107
107
120
120
117
117
114
116
120
107
113
120
109
115
120
Current limit (% of
rated output current)
120
Carrier frequency
(kHz)
*5
10
10
10
8
10
15
15
8
10
10
10
10
5
5
8
2
2
2
Maximum output
frequency
400.0Hz
Maximum output voltage
3-phase; 200, 208, 220, 230, or 240Vac
(Proportional to input voltage)
*1 The difference between Heavy Duty ratings and the Normal Duty ratings for the Drive are the rated input and output current, overload capacity, carrier frequency, current limit, and
maximum output frequency. Parameter C6-01 must be set to value of “0” for Heavy Duty ratings and “2” for Normal Duty ratings. Factory default is Heavy Duty (C6-01=0).
*2 Horsepower ratings are based on 230V or 460V NEC Table 430.150. The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor
and Drive, be sure that the Drive's rated output current is appropriate for the motor's rated current.
*3 Models 2110, 4220, 4300 have an overload rating of 120% of rated output current for 60 seconds.
*4 2kHz is the Maximum carrier frequency value and default carrier frequency value for all models.
*5 Each value shown is the Maximum carrier frequency and default carrier frequency.
O
utpu
t rat
ing
s
Heavy D
uty
*1
Norma
l Duty
*1
Содержание Varispeed f7
Страница 1: ...F7 Drive Programming Manual Model CIMR F7U Document Number TM F7 02...
Страница 2: ......
Страница 8: ...vi Notes...
Страница 158: ...Programming 150 Notes...