Programming 129
L6-04 Torque Detection Selection 2
L6-05 Torque Detection Level 2
Setting Range:
0 to 300% of Drive rated output current
Factory Default: 150% of Drive rated output current
L6-06Torque Detection Time 2
Setting Range:
0.0 to 10.0 Seconds
Factory Default: 10.0 Seconds
Torque detection 2 functions the same way as torque detection selection 1. The multi-function outputs associated with torque
detection 2 are torque detection 2 N.O. and torque detection 2 N.C. (H2-0x = 18 and 19, respectively). See parameter
description above for details.
L7 Torque Limit
L7-01 Forward Torque Limit
L7-02 Reverse Torque Limit
L7-03 Forward Regenerative Torque Limit
L7-04 Reverse Regenerative Torque Limit
Setting Range:
0 to 300 %
Factory Default: 200%
The torque limit function limits the amount of motor torque in all four quadrants of vector control operation:
· Forward Motoring
· Forward Regenerating
· Reverse Motoring
· Reverse Regenerating
Setting
Description
0
Disabled (
factory default
)
1
OL3 at Speed Agree - Alarm
2
OL3 at Run - Alarm
3
OL3 at Speed Agree - Fault
4
OL3 at Run - Fault
5
UL3 at Speed Agree - Alarm
6
UL3 at Run - Alarm
7
UL3 at Speed Agree - Fault
8
UL3 at Run - Fault