Sigma II User’s Manual
Chapter 7: Using the Digital Operator
7 - 29
Manual Adjustment of Speed Reference Offset
Follow the procedure below to manually adjust the speed reference offset.
Using the Hand-held Digital Operator
1.
Press the
DSPL/SET
key to select the auxiliary function mode.
2.
Select the parameter Fn00A.
Press the
Up Arrow
or
Down Arrow
key to select the digit.
Press the
Up Arrow
or
Down Arrow
key to change the value.
3.
Press the
DATA/ENTER
key, and the display will be as shown below. The
manual adjustment mode for the speed reference offset will be entered.
4.
Turn ON the Servo ON (/S-ON) signal. The display will be as shown below.
5.
Press the
Left Arrow
or
Right Arrow
key, to display the speed reference
offset amount.
6.
Press the
Up Arrow
or
Down Arrow
key to adjust the amount of offset
(adjustment of the speed reference offset).
7.
Press the Right Cursor Key to return to the display shown in the above step 4.
8.
Press the
DATA/ENTER
key to return to the auxiliary function mode display.
This completes the speed reference offset manual adjustment.
Using the Built-in Panel Operator
1.
Press the
MODE/SET
key to select the auxiliary function mode.
SGDM-
MODE/SET
DATA/
CHARGE
POWER
SERVOPACK
200V
YASKAWA
Содержание SGMAH
Страница 1: ...Sigma II Series Servo System User s Manual...
Страница 2: ......
Страница 4: ...ii This page intentionally left blank...
Страница 6: ...iv This page intentionally left blank...
Страница 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Страница 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Страница 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Страница 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Страница 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Страница 487: ......