Sigma II User’s Manual
Chapter 7: Using the Digital Operator
7 - 9
5.
Press the
DATA/ENTER
key to store the data. The display will flash.
6.
Press the
DATA/ENTER
key again to return to the parameter number display.
This procedure has changed the setting of the parameter Pn507 from 100 to 85.
Repeat steps 2 to 6 to change the setting again.
Example Using the Built-in Panel Operator
1.
Press the
MODE/SET
key to select the parameter setting mode.
2.
Press the
Up Arrow
or
Down Arrow
key to select the parameter number to
set. (Pn507 is selected in this example.)
3.
Press the
DATA/SHIFT
key for a minimum of one second to display the current
data for the parameter selected in step 2.
4.
Press the
Up Arrow
or
Down Arrow
key to change to the desired value of
“00085”.
As you keep pressing the
Up Arrow
AND
Down Arrow
keys, and the
display changes faster.
5.
Press the
DATA/SHIFT
key for a minimum of one second to save the data. The
display will flash.
6.
Press the
DATA/SHIFT
key once more for a minimum of one second to display
the parameter number again.
This has changed the setting of the parameter Pn507 from 100 to 85.
SGDM-
MODE/SET
DATA/
CHARGE
POWER
SERVOPACK
200V
YASKAWA
Содержание SGMAH
Страница 1: ...Sigma II Series Servo System User s Manual...
Страница 2: ......
Страница 4: ...ii This page intentionally left blank...
Страница 6: ...iv This page intentionally left blank...
Страница 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Страница 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Страница 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Страница 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Страница 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Страница 487: ......