![YASKAWA SGMAH Скачать руководство пользователя страница 237](http://html.mh-extra.com/html/yaskawa/sgmah/sgmah_user-manual_3716675237.webp)
Sigma II User’s Manual
Chapter 6: Servo Adjustment
6 - 9
Related Parameters
Switch
Parameters
Caution
1. Exercise caution when setting the notch frequencies. Do not set the notch frequencies close to the speed
loop’s response frequency. Notch filter frequency should be at least 4 times higher than the speed loop’s
response frequency. Setting the notch frequency too close to the response frequency may cause vibration
and damage the machine. The speed loop’s response frequency is the speed loop gain (Pn100) when the
inertia ratio (Pn103) is set to the correct value.
2. Change the notch filter frequency (Pn409 & Pn40B) only when the motor is stopped. Vibration may occur
if the notch filter frequency is changed while the motor is rotating, causing damage to the machine.
Parameter
No.
Digit
Place
Parameter Name
Setting
Description
Factory
Setting
Pn408
0
Notch filter selection
0
Disabled
0
1
Enabled
1
Fixed parameter
–
–
–
2
Second stage notch filter
selection
0
Disabled
0
1
Enabled
3
Fixed parameter
–
–
–
Parameter
No.
Name
Unit
Setting Range
Factory Setting
Pn40A
Notch filter Q value
0.01
50 to 400
70
Pn40B
Second stage notch filter frequency
Hz
50 to 2000
2000
Pn40C
Second stage notch filter Q value
0.01
50 to 400
70
Содержание SGMAH
Страница 1: ...Sigma II Series Servo System User s Manual...
Страница 2: ......
Страница 4: ...ii This page intentionally left blank...
Страница 6: ...iv This page intentionally left blank...
Страница 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Страница 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Страница 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Страница 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Страница 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Страница 487: ......