Sigma II User’s Manual
Chapter 5: Parameter Settings and Functions
5-103
Multi-turn Setup Using the Built-in Panel Operator
1.
Press the
MODE/SET
key to select the auxiliary function mode.
2.
Press the
Up Arrow
or
Down Arrow
key to select the parameter Fn013.
3.
Press the
DATA/SHIFT
key. The following display will appear.
4.
Press the
MODE/SET
key. The display will change as follows, and the absolute
encoder’s multi-turn limit setting operation will be performed.
5.
Press the
DATA/SHIFT
key to return to the auxiliary function mode.
This completes the absolute encoder’s multi-turn limit setting operation. Cycle the
power to the servo amplifier.
•
The multi-turn limit value should be changed only for special applications
.
Changing it inappropriately or unintentionally can be dangerous.
•
If the Multi-turn Limit Value Disagreement Alarm occurs, check the setting of parameter Pn205 in
the servo amplifier to be sure that it is correct. If Fn013 is executed when an incorrect value is set in
Pn205, that same incorrect value will be set in the encoder. There will not be an additional alarm,
even if an incorrect value is set, but incorrect positions will be detected.
This results in a potentially dangerous situation where the machine will move to an unexpected position.
Flashes for
1 second.
Flashes for
1 second.
WARNING
Содержание SGMAH
Страница 1: ...Sigma II Series Servo System User s Manual...
Страница 2: ......
Страница 4: ...ii This page intentionally left blank...
Страница 6: ...iv This page intentionally left blank...
Страница 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Страница 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Страница 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Страница 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Страница 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Страница 487: ......