6.1 I/O Signal Allocations
6.1.10 Speed Limit during Torque Control
6
Application Function
s
6-15
Selecting the Speed Limit
The smaller of the external speed limit and internal speed limit will be used.
Internal Speed Limiting
Set the speed limit for the motor in Pn407 (Speed Limit during Torque Control) or Pn480
(Speed Limit during Force Control).
Also set Pn408 = n.
X
(Speed Limit Selection) to specify using the maximum motor speed
or the overspeed alarm detection speed as the speed limit. Select the overspeed alarm detec-
tion speed to limit the speed to the equivalent of the maximum motor speed.
Note: If you are using a Rotary Servomotor, set Pn407 (Speed Limit during Torque Control). If you are using a Linear
Servomotor, set Pn480 (Speed Limit during Force Control).
•
Rotary Servomotors
•
Linear Servomotors
Note: If the parameter setting exceeds the maximum speed of the Servomotor, the Servomotor’s maximum speed
or the overspeed alarm detection speed will be used.
External Speed Limiting
The motor speed will be limited by VLIM (Limit Speed for Torque Control). Refer to the following
manual for details.
Σ
-7-Series MECHATROLINK-III Communications Standard Servo Profile Command Manual (Manual No.: SIEP
S800001 31)
Parameter
Meaning
When Enabled
Classification
Pn002
n.
0
Reserved setting (Do not use.)
After restart
Setup
n.
1
(default setting)
Use the speed limit from the VLIM (Limit
Speed for Torque Control) command as the
speed limit. (Use external speed limiting.)
Parameter
Meaning
When Enabled
Classification
Pn408
n.
0
(default setting)
Use the smaller of the maximum motor speed
and the setting of Pn407 or Pn480 as the
speed limit.
After restart
Setup
n.
1
Use the smaller of the overspeed alarm detec-
tion speed and the setting of Pn407 or Pn480
as the speed limit.
Pn407
Speed Limit during Torque Control
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 min
-1
10000
Immediately Setup
Pn480
Speed Limit during Force Control
Setting Range
Setting Unit
Default Setting
When Enabled
Classification
0 to 10,000
1 mm/s
10000
Immediately
Setup
Torque