404
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
Model
Rated Current (A)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2346
346.0
346.0
294.3
259.8
-
-
2415
415.0
415.0
365.2
332.0
-
-
Table 9.11 Carrier Frequency and Rated Current Derating (400 V Class)
Model
Rated Current (A)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
4002
1.8
1.8
1.8
1.6
1.3
1.0
4003
3.4
3.4
3.4
2.9
2.3
1.7
4005
4.8
4.8
4.8
4.3
3.7
3.0
4006
5.5
5.5
5.5
4.9
4.1
3.2
4007
7.2
7.2
7.2
6.5
5.6
4.8
4009
9.2
9.2
9.2
8.1
6.8
5.4
4015
14.8
14.8
14.8
13.1
11.0
8.9
4018
18.0
18.0
18.0
15.9
13.4
10.8
4024
24.0
24.0
24.0
21.2
17.7
14.1
4031
31.0
31.0
31.0
27.5
23.0
18.6
4039
39.0
39.0
39.0
34.5
29.0
23.4
4045
45.0
45.0
45.0
39.1
31.8
24.4
4060
60.0
60.0
60.0
53.1
44.6
36.0
4075
75.0
75.0
75.0
66.4
55.7
45.0
4091
91.0
91.0
91.0
80.6
67.6
54.6
4112
112.0
112.0
91.8
78.4
-
-
4150
150.0
150.0
123.0
105.0
-
-
4180
180.0
180.0
147.6
126.0
-
-
4216
216.0
216.0
177.1
151.2
-
-
4260
260.0
260.0
213.2
182.0
-
-
4304
304.0
304.0
249.3
212.8
-
-
4371
371.0
371.0
304.2
259.7
-
-
4414
389.0
324.8
-
-
-
-
4453
453.0
378.3
-
-
-
-
4605
605.0
505.2
-
-
-
-
■
Altitude Derating
Install the drive in a location that with an altitude of 1000 m (3281 ft.) or lower.
Derate the output current by 1% for each 100 m (328 ft.) to install the drive in altitudes between 1000 m to 4000
m (3281 ft. to 13123 ft.).
It is not necessary to derate the rated voltage in these conditions:
•
Installing the drive at 2000 m (6562 ft.) or lower
•
Installing the drive between 2000 m to 4000 m (6562 ft. to 13123 ft.) and grounding the neutral point on the
power supply.
Contact Yaskawa or your nearest sales representative when the drive is not grounded with the neutral network.