YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
623
Coded Output
(Binary)
Description
DO-A3 Terminal Block TB2
Terminals P1-PC
Terminals P2-PC
Terminals P3-PC
Terminals P4-PC
A
oL1 [Motor
Overload]
0
1
0
1
B
Not used
1
1
0
1
C
Uv1, Uv2
[Undervoltage], Uv3
[Soft Charge
Answerback Fault]
0
0
1
1
D
dEv [Speed
Deviation]
1
0
1
1
E
PGo [Encoder (PG)
Feedback Loss]
0
1
1
1
F
Not used
1
1
1
1
*1
The digits represented by xx vary depending on the type of fault that occurs.
Digital Output Card Selection
Refer to
“
H2: Multi-function Digital Output
”
for more information about the functions that output from the
terminals when
F5-09 = 2 [DO-A3 Output Mode Selection = Programmable (F5-01 to F5-08)]
. Use
F5-01 to F5-
08
to set the output items.
No.
Name
Setting Range
Default
F5-01
Terminal P1-PC Function Select
0 - 192
0: During Run
F5-02
Terminal P2-PC Function Select
0 - 192
1: Zero Speed
F5-03
Terminal P3-PC Function Select
0 - 192
2: Speed Agree 1
F5-04
Terminal P4-PC Function Select
0 - 192
4: Frequency Detection 1
F5-05
Terminal P5-PC Function Select
0 - 192
6: Drive Ready
F5-06
Terminal P6-PC Function Select
0 - 192
37: During Frequency Output
F5-07
Terminal M1-M2 Function Select 0 - 192
F: Not Used
F5-08
Terminal M3-M4 Function Select 0 - 192
F: Not Used
F5-01: Terminal P1-PC Function Select
No.
(Hex.)
Name
Description
Default
(Range)
F5-01
(0399)
Terminal P1-PC
Function Select
The function output from terminal P1-PC on the DO-A3 card is selected by
the MFDO setting value. This parameter is enabled when
F5-09 = 2 [DO-
A3 Output Mode Selection = Programmable (F5-01 to F5-08)]
.
0
(0 - 1FF)
F5-02: Terminal P2-PC Function Select
No.
(Hex.)
Name
Description
Default
(Range)
F5-02
(039A)
Terminal P2-PC
Function Select
The function output from terminal P2-PC on the DO-A3 card is selected by
the MFDO setting value. This parameter is enabled when
F5-09 = 2 [DO-
A3 Output Mode Selection = Programmable (F5-01 to F5-08)]
.
1
(0 - 1FF)
F5-03: Terminal P3-PC Function Select
No.
(Hex.)
Name
Description
Default
(Range)
F5-03
(039B)
Terminal P3-PC
Function Select
The function output from terminal P3-PC on the DO-A3 card is selected by
the MFDO setting value. This parameter is enabled when
F5-09 = 2 [DO-
A3 Output Mode Selection = Programmable (F5-01 to F5-08)]
.
2
(0 - 1FF)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV