496
YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
■
S6: Overtorque Detection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S6-01
(06B6)
OverT Detect
Operation Select 1
Sets whether to enable or disable overtorque detection, the detection
conditions, and the drive operation after detection of faults.
0 : Disabled
1 : oL3 @ Speed Agree - Alarm only
2 : oL3 @ RUN - Alarm only
3 : oL3 @ Speed Agree - Fault
4 : oL3 @ RUN - Fault
5 : oL3 @ Speed Agree - Alarm only2
6 : oL3 @ RUN - Alarm only2
0
(0 - 6)
S6-02
(06B7)
Overtorque
Detection Level 1
Sets the level to trigger an overtorque.
150%
(0 - 300%)
S6-03
(06B8)
Overtorque
Detection Time 1
Sets the overtorque detection time 1.
0.1 s
(0.0 - 10.0 s)
S6-04
(06B9)
OverT Detect
Operation Select 2
Sets whether to enable or disable overtorque detection, the detection
conditions, and the drive operation after detection of faults.
0 : Disabled
1 : oL3 @ Speed Agree - Alarm only
2 : oL3 @ RUN - Alarm only
3 : oL3 @ Speed Agree - Fault
4 : oL3 @ RUN - Fault
5 : oL3 @ Speed Agree - Alarm only2
6 : oL3 @ RUN - Alarm only2
0
(0 - 6)
S6-05
(06BA)
Overtorque
Detection Level 2
Sets the level to trigger an overtorque.
150%
(0 - 300%)
S6-06
(06BB)
Overtorque
Detection Time 2
Sets the overtorque detection time 2.
0.1 s
(0.0 - 10.0 s)
S6-09
(1A93)
Torque Detection
Filter Time
Sets the time constant for a primary filter to the torque reference or
to the output current used to detect overtorque.
0 ms
(0 - 1000 ms)
◆
T: Motor Tuning
■
T0: Tuning Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
T0-00
(1197)
Tuning Mode
Selection
Sets the type of Auto-Tuning to be used.
0 : Motor Parameter Tuning
1 : Control Tuning
0
(0, 1)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV