YASKAWA ELECTRIC
SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
595
E : Const Trq, 60 Hz base, 180 Hz max
This pattern is used to rotate motors at greater than 60 Hz. Output voltage is constant when operating at greater
than 60 Hz.
Note:
The voltage values in the figure represent those when using 200 V class drives. Double the values for 400 V class drives.
2003 - 2018, 4002 - 4009
2025 - 2180, 4015 - 4091
2215 - 2415, 4112 - 4605
F : Custom
Enables a custom V/f pattern by changing
E1-04 to E1-13 [V/f Pattern for Motor 1]
.
The default settings are equivalent to setting value
1 [Const Trq, 60Hz base, 60Hz max]
.
E1-04: Maximum Output Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency.
Determined by A1-02
(Determined by A1-
02)
E1-05: Maximum Output Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-05
(0304)
Maximum Output
Voltage
Sets the maximum output voltage for the V/f pattern.
Determined by A1-02
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
E1-06: Base Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-06
(0305)
Base Frequency
Sets the base frequency.
Determined by A1-02
(0.0 to E1-04)
E1-07: Mid Point A Frequency
No.
(Hex.)
Name
Description
Default
(Range)
E1-07
(0306)
Mid Point A
Frequency
Sets a middle output frequency for the V/f pattern.
Determined by A1-02
(0.0 - E1-04)
E1-08: Mid Point A Voltage
No.
(Hex.)
Name
Description
Default
(Range)
E1-08
(0307)
Mid Point A Voltage
Sets the middle output frequency.
Determined by A1-02
(200 V Class: 0.0 -
255.0 V,
400 V Class: 0.0 -
510.0 V)
Note:
Default setting is determined by
A1-02 [Control Method Selection]
and
o2-04 [Drive Model (KVA) Selection]
.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV