SIEP C710617 19A YASKAWA AC Drive CR700 Technical Manual
615
F2-02: Analog Input Option Card Gain
No.
(Hex.)
Name
Description
Default
(Range)
F2-02
(0368)
RUN
Analog Input Option
Card Gain
Sets the analog reference gain as a percentage when the maximum output
frequency is 100%.
100.0%
(-999.9 - +999.9%)
Note:
Set
F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together]
to enable this function.
F2-03: Analog Input Option Card Bias
No.
(Hex.)
Name
Description
Default
(Range)
F2-03
(0369)
RUN
Analog Input Option
Card Bias
Sets the analog reference bias as a percentage when the maximum output
frequency is 100%.
0.0%
(-999.9 - +999.9%)
Note:
Set
F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together]
to enable this function.
■
F3: Digital Input Option
F3 parameters
set the type of input signal to use with digital input option card DI-A3.
Use these digital inputs to set the frequency reference when you install the DI-A3 card in a drive. Set
b1-01 = 3
[Frequency Reference Selection 1 = Option PCB]
to use this card as the frequency reference input. The input
signal is isolated input of 24 Vdc and 8 mA.
•
Binary, 16-bit/BCD, 4-digit input
•
Binary, 12-bit/BCD, 3-digit input
•
Binary, 8-bit/BCD, 2-digit input
You can also use the DI-A3 card as an MFDI, if the setting of
F3-01
is correct.
WARNING
Sudden Movement Hazard. Do test runs and examine the drive to make sure that command references are
configured correctly. If you set the command reference incorrectly, it can cause death, serious injury, or equipment damage from
unwanted motor rotation.
MFDI for DI-A3
When you set to
F3-01 = 8 [Digital Input Function Selection = Multi-Function Digital Input]
, you can use the
digital input option DI-A3 as the multi-function input. To use this as the multi-function input, set such that
b1-01
≠ 3 [Frequency Reference Selection 1 ≠ Option PCB]
.
Select the function for the DI-A3 terminals with
F3-10 to F3-25 [Terminal D0 to DF Function Selection]
.
Note:
•
Refer to
H1-xx
“
MFDI Function Selections
”
for more information about multi-function digital input setting values.
•
You cannot set
20 to 2F [External Fault]
to
F3-10
to
F3-25
.
•
Set
F3-10 to F3-25 = F [Not Used]
when not using the DI-A3 multi-function input. The through mode function is not supported.
•
Terminal Dx of the DI-A3 is read twice in accordance with the setting of
b1-06 [Digital Input Reading]
.
•
If you set
F3-01 = 8
when DI-A3 is the frequency reference source (
b1-01 or b1-15 = 3 [Frequency Reference Selection 1/2 = Option
PCB]
), the drive will detect
oPE05 [Run Cmd/Freq Ref Source Sel Err]
.
•
The following functions can be used together with the DI-A3 multi-function input.
–
H1-40 to H1-42 [Mbus Reg 15C0h bit0 to bit2 Input Func]
–
H7-01 to H7-04 [Virtual Multi-Function Inputs 1 to 4]
F3-01: Digital Input Function Selection
No.
(Hex.)
Name
Description
Default
(Range)
F3-01
(0390)
Digital Input
Function Selection
Sets the data format of digital input signals. Set
o1-03 = 0 or 1 [Frequency
Display Unit Selection = 0.01 Hz or 0.01% (100% = E1-04)]
to enable this
function.
0
(0 - 8)
Note:
The input signal type is BCD when
o1-03 = 2 or 3 [Revolutions Per Minute (RPM) or User Units (o1-10 & o1-11)]
. The
o1-03
value
sets the setting units.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV