OFF : The brake is tightened.
Note:
Refer to
for details.
22: Overload Detection (N.O.)
Setting
Function
Description
22
Overload Detection
(N.O.)
The terminal turns ON when the overload is detected.
Note:
Refer to
Overload Detection on page 190
for details.
23: Weight Det N.C.
Setting
Function
Description
23
Weight Det N.C.
The terminal turns OFF when the overload is detected.
Note:
Refer to
Overload Detection on page 190
for details.
2F: Maintenance Notification
Setting
Function
Description
2F
Maintenance
Notification
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
•
IGBT
•
Cooling fan
•
Capacitor
•
Soft charge bypass relay
Note:
Refer to
“
Alarm Outputs for Maintenance Monitors
”
for more information.
30: During Torque Limit
Setting
Function
Description
30
During Torque Limit
The terminal activates when the torque reference is the torque limit set with
L7 parameters
,
H3-02
,
H3-06
, or
H3-10 [MFAI Function Select]
.
Note:
Refer to
“
L7: Torque Limit
”
for more information.
33: Zero Servo Complete
Setting
Function
Description
33
Zero Servo Complete
The terminal activates when positioning in the range set with
b9-02 [Zero Servo Completion
Window]
completes after sending the Zero-Servo command.
Note:
Refer to
“
b9: Zero Servo
”
for more information.
37: During Frequency Output
Setting
Function
Description
37
During Frequency
Output
The terminal turns on when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV