4 Option Components
YASKAWA ELECTRIC
TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
11
Figure 3
Figure 3 Option Modular Connector (CN1)
u
Option LED Display
n
Defining Option LED States
Figure 4
Figure 4 Option LED Labels
Table 4 Option LED States
Name
Indication
Operating Status
Description
Color
Status
L.RUN
Green
ON
Normal operation
Receiving data normally
OFF
Timed out
• Timed out waiting to receive
• Logging onto the network
• During reset
L.ERR
Red
ON
CRC error
• CRC error
• Station address setting error (F6-10 = 0)
OFF
During
communications
• Normal communications
• During reset
SD
Red
ON
Sending data
Sending data
Note:
LED may appear to flash with slower
baud rates.
OFF
No data transfer
• No data being sent
• During reset
Top View
DA
1
2
3
4
5
DB DG SLD SLD
Side View
1
2
3
4
5
L.ERR
RD
L.RUN
SD
GA700 and GA800 Label
1000-Series Label