7 Basic Functions
36
YASKAWA ELECTRIC
TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
n
Access Method to Parameter of MEMOBUS Register Number 1000H or
Later
When setting and reading parameters of the MEMOBUS register number 1000H or later
from the PLC, set the MEMOBUS register number 1000H or later to the register number
0C00H to 0C0FH from the CC-Link communications. The user can access the value of the
parameters 1000H or later specified by the MEMOBUS register number 0C00H to 0C0FH
with the register number 0C80H to 0C8FH.
This function is available in the option versions PRG:0103 and later.
Table 8 List of MEMOBUS Register Numbers and Descriptions
MEMOBUS Register
Number
Descriptions
0C00H
Register number setting 1
0C01H
Register number setting 2
0C02H
Register number setting 3
0C03H
Register number setting 4
0C04H
Register number setting 5
0C05H
Register number setting 6
0C06H
Register number setting 7
0C07H
Register number setting 8
0C08H
Register number setting 9
0C09H
Register number setting 10
0C0AH
Register number setting 11
0C0BH
Register number setting 12
0C0CH
Register number setting 13
0C0DH
Register number setting 14
0C0EH
Register number setting 15
0C0FH
Register number setting 16
0C80H
Parameter contents of register number in setting 1
0C81H
Parameter contents of register number in setting 2
0C82H
Parameter contents of register number in setting 3
0C83H
Parameter contents of register number in setting 4
0C84H
Parameter contents of register number in setting 5
0C85H
Parameter contents of register number in setting 6
0C86H
Parameter contents of register number in setting 7
0C87H
Parameter contents of register number in setting 8
0C88H
Parameter contents of register number in setting 9
0C89H
Parameter contents of register number in setting 10
0C8AH
Parameter contents of register number in setting 11
TOBP_C730600_83C_3_0_E.fm 36 ページ 2018年10月24日 水曜日 午後5時59分