5 Installation Procedure
20
YASKAWA ELECTRIC
TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
5.
Select the proper CC-Link dedicated communication cable according to
Table 6
.
Route the option wiring inside the enclosure as shown in
Figure 11
-B. Take proper
precautions so that the front covers will easily fit back onto the drive.
Users may also choose to route the option wiring through openings on the front
cover of some models. Remove the perforated tabs on the left side of the front cover
as shown in
Figure 11
-A to create the necessary openings on these models.
Refer to the Peripheral Devices & Options section of the drive instruction manual for
more information.
Note: 1.
Separate communication cables from main circuit wiring and other electrical lines to avoid potential
sources of electrical interference.
2.
Connect the terminator (model No.: JEPMC-W6022-E) to the option modular connector (CN1) on the
end drive of the communication lines.
Figure 11
Figure 11 Wire Routing Examples
B
A
TOBP_C730600_83C_3_0_E.fm 20 ページ 2018年10月24日 水曜日 午後5時59分