6 Related Drive Parameters
34
YASKAWA ELECTRIC
TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
<1> Set b1-02 = 3 to start and stop the drive with the CC-Link master device using serial communications.
Set b1-01 = 3 to control the frequency reference of the drive via the master device.
<2> Set the voltage reference of D1000 with the CC-Link master device using the voltage reference of the D1000, set
b1-18 to 3.
<3> Setting this parameter to 3 or 4 will cause the drive to continue operation after detecting a fault. Take proper
measures such as installing an emergency stop switch when using settings 3 or 4.
<4> Refer to the drive manual to know if settings 4 and 5 are available. Settings 4 and 5 are available in A1000
software versions PRG: 1021 and later.
<5> The setting range for 1000-Series drives is different for different software versions. Refer to the instruction
manual of a specific drive for more information.
<6> The default setting is 2.0 s, but this default setting will automatically be changed to 0.0 s when CC-Link option is
connected.
<7> When using D1000, the name and description will differ as follows.
<Name>
Torque Reference/Torque Limit Selection from Communications Option
<Description>
Enables or disables the torque reference or torque limit.
0: Enabled
1: Disabled
<8> Control method availability of this parameter depends on product series.
1000-Series Drives: Parameter is available in CLV, AOLV/PM, and CLV/PM.
In AOLV/PM, this value is read as the Torque Limit.
GA700, GA800 Drives: Parameter is available in OLV, CLV, AOLV, AOLV/PM, CLV/PM, and EZOLV.
In OLV and EZOLV, this value is read as the Torque Limit.
<9> The setting specifies that network communications provide the torque reference or torque limit. The motor may
not rotate if the PLC does not supply a torque reference or torque limit.
<10> Cycle power for setting changes to take effect.
<11> All station addresses must be unique.
<12> A total of 42 nodes can be connected, assuming that all connections are drives.
The following conditions apply when connecting devices that are other drives or energy-saving units to the network:
A: number of remote I/O nodes........ 64 max
B: number of remote device nodes... 42 max
C: number of local nodes.................. 26 max
a: number of drives that occupies 1 node
b: number of drives that occupies 2 nodes
c: number of drives that occupies 3 nodes
d: number of drives that occupies 4 nodes
{(1
×
a)+(2
×
b)+(3
×
c)+(4
×
d)}
≤
64
{(16
×
A)+(54
×
B)+(88
×
C)}
≤
2304
(
(
)
)