The XTBA QUICK SET UP GUIDE TO DALI 

If you have just walked into an installation, you are in a hurry and the client is 
in  the  corner  sharpening  an  axe,  then  the  following  might  be  useful  to  save 
you reading through the delights of the entire manual! 

Installation installed and connected but not set up or much else?  

1 - Plug in the mains adaptor first and then connect the XTBA DALI Watch to 
any point of the DALI cable. 

2  -  Is  the  blue  LED flashing?  If  no  go  to  3. If  flashing  there  is  no  DALI  buss 
power so you need to add one as follows: Press the function key until: 

 

L  O  C  A  L   

B  U  S  S   

P  S  U   

O  F  F 

 

 

 

 

 

Y  e  s   

t  o   

t  o  g  g  l  e   

 

 

 
Press the Yes key to turn on the power and then the function key to get back 
to the main menu loop. 

3 – Press the function key until: 

D  I  S  C  O  V  E  R   

P  R  O  G  R  A  M   

A  L  L 

y  e  s   

t  o   

e  n  t  e  r   

o  r   

m  e  n  u 

 
4 – Press the Yes button and the message ‘WILL ERASE ALL DATA’ will be 
displayed. Press Yes again to start discovery. 

5 – The XTBA DALI Watch will erase all data and discover the first device, at 
the end of the search the device to be programmed will be lit to 50% and the 
display will go to:  

S  .  A  D  D  R  E  S  S   

=     

1   

 

 

 

 

 

m  e  N  u  =  r  e  j  e  c  t    y  e  s  =  s  e  n  d 

 
Using the up/down keys set the address you would like the device to be and 
then press Yes. 

6 – Repeat step 5 until COMPLETE (number of devices) FOUND displays. 

7 – The devices will have had their defaults set in discovery as follows: 

Power On Level = 1, Minimum Level = 1, System Failure Level = 0, Max Level 
= 254. Following discovery you can change these settings in Quick Set Up if 
needed.  

Check it all worked 

8 – Press the Function button until TRANSMIT DALI and press Menu, press 
Menu until ADJUST ONE LEVEL appears then press Yes and the display will 
change to: 

  A  D  D  R  E  S  S   

  1   

 

T  O   

 

 

0  % 

  L  /  R  =   

A  D  D    U  /  D  =   

L  E  V  E  L 

Содержание DALI Watch

Страница 1: ...2013 XTBA 1986 2013 XTBA DALI WATCH DALI Tester ISSUE 1 10 03 13 Software V3 45 or later If you are in a rush see Quick Set Up on the last page 35 Fernleigh Road London N21 3AN 44 0 208 882 0100 44 0 208 882 9326 e mail dmx xtba co uk www xtba co uk ...

Страница 2: ...ower from an existing DALI Buss Power Supply 4 DALI Buss Power from the XTBA DALI Watch 4 XTBA DALI Watch Button Control 5 Main Menu Loop 5 Receive Menu Loop 6 Transmit Menu Loop 9 DALI Parameters 18 Device Response Time 18 Bit and Word Time 18 Bit Time 18 Word Time 18 Device Response Time 19 User Options 19 Reference 21 DALI COMMANDS 21 DALI HIGH COMMANDS 23 The XTBA QUICK SET UP GUIDE TO DALI 24...

Страница 3: ...NATE command 256 to ENABLE DEVICE TYPE command 272 are referred to high commands DALI also helpfully as it uses less bits has a channel address range from 0 to 63 rather than 1 to 64 and in order to keep as close as possible to the DALI standard the XTBA DALI Watch sticks to this format To simplify in day to day use the default address loaded on a functions entry is 1 rather than 0 so you can get ...

Страница 4: ...d another power supply How can you tell First connect the XTBA DALI Watch to the DALI data pair When connected to the DALI system and in the main menu loop if the blue led is off the system already has DALI Buss Power connected So you can now use the XTBA DALI Watch If the blue LED is flashing quickly there is no DALI Buss Power available so you will need to add power to the Buss Press the Functio...

Страница 5: ... stored so the XTBA DALI Watch will go back to the setting in user options on next power up In menus where the Left Right buttons are used pressing both will set the value to 1 In menus where the Up Down buttons are used for levels pressing both together will set the value to 50 DALI Buss Power Alert On entry to functions except User Options the XTBA DALI Watch will check that DALI Buss Power is a...

Страница 6: ...ommands received If level blocking is enabled only non level commands will be received The XTBA DALI Watch will only display new commands so if a single command is sent again it will be ignored after the first time unless repeat command blocking is turned off Pressing the Yes button with the View Commands Live menu displayed the display might look like this once a command has been received Command...

Страница 7: ... 0 0 0 Short address 0 with command 0 OFF The upper line displays the short address group or ALL for a broadcast command Note bit 0 is set for 1 the command bit as OFF is a command the address is contained in bits 1 through 6 If level blocking is turned off and a level is being received the display should look something like this S A D D 0 L e v N o 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Short address 0 ...

Страница 8: ...ll loop through the short address S ADD Group or broadcast B CAST In this way any command can be set up to be compared Pressing Yes will take you into the compare display O F F A D D R E S S 0 Pressing the Menu button will toggle the left side arrow to the upper or lower line With the arrow in the upper line pressing the Up Down buttons will change the command to be compared With the arrow on the ...

Страница 9: ...G DATA Incoming address and command or level information is now compared with the internal memory and if any differences detected the first error detected will be displayed as follows C H A N O R I G N E W 0 3 1 2 6 In this case address 0 has moved from 31 to 26 during the sample time Transmit Menu Loop Adjust single levels Adjust One Level Adjust All Levels Global all Levels Adjust Group Levels D...

Страница 10: ...ven close there will be a delay from the display and the fixture getting to that level Adjust One Level Pressing the Yes button will enter the function and the display will change to This allows you to alter all DALI levels to quickly find a fixture A D D R E S S 1 T O 0 L R A D D U D L E V E L Pressing the Left Right buttons will alter the address setting and the Up Down the level Adjust All Leve...

Страница 11: ...ess Set Up Scenes Check Fixtures Quick Set Up In order to set up DALI fixtures values need to be transferred to the data transfer register before the set up command transfers the value to the relevant device slot and all commands sent twice in less than 100ms This would take some speedy finger action so the XTBA DALI Watch deals with all of this for you so you don t need to bother Pressing the Yes...

Страница 12: ...n the display will change to S E T U P A T S H O R T A D D R y E s t o e n t e r o r m E n u Pressing the Menu button again will loop through short address S ADD Group or broadcast B CAST This allows all types of set up If broadcast is selected the Watch will display SET UP ALL DEVICES To warn you that you are about to globally change all connected devices Pressing Yes will take you into the advan...

Страница 13: ... the information clearer the Watch will show which type of data requested is returned For example if Query Max Level is set the answer will be displayed as LEV as it is a level If Query Random address the answer will be displayed as VAL as it is a value YES NO Beware the YES No requests If a YES NO request is sent and the answer is YES the device will return 0xFF d 255 If the answer is No nothing ...

Страница 14: ... S 2 5 4 1 2 3 0 2 1 On the lower line you will see the search address being scanned through In reality this tells you next to nothing but at least you can see something is going on and is fun to watch Once a device has been discovered that fixture will light to the display find value set in user options default 50 so you can see which it is and the display will change to S A D D R E S S 1 m e n u...

Страница 15: ...o Discover Program New If new fixtures are added to an existing system their short address can be assigned without the need to go through the entire discovery process Pressing Yes when the Discover Program New is displayed will enter new device search If new devices are found the Watch will switch into program mode as in Discover Program All and the new devices short address can be programed Exist...

Страница 16: ... address of the fixture to be changed will be lit and when the arrow moves to the lower line the address to be change to will be lit if connected Remove Short Address If there are two fixtures on an address that need to be on different addresses this function allows the address to be removed as there is no other way to separate the fixtures Following the addresses removal Discover New can be run a...

Страница 17: ... T o c o n t i n u e In this case address 5 has a different max level Pressing the Yes button will continue the search At the end of the search the display will change to 8 D E V I C E S F O U N D f u n c t I o n t o e s c a p e This will display the number of valid addresses found So you can tell how many active devices are on the system and if they are set up to the same defaults If any differen...

Страница 18: ...Yes button with bit time displayed the display might look like this Bit and Word Time B I T T I M E W O R D T I M E 8 4 0 m s O K 1 4 0 m s O K On the right of the value will be OK if the time is in range or ERR if out of the DALI specification Bit Time The DALI protocol uses bi phase encoding so it is difficult to measure the full bit length in a data stream The Watch measures the half bit time a...

Страница 19: ...w value should be between 0 and 6 5 volts D A L I I N P U T V O L T A G E L O W 0 0 V H I G H 1 5 1 V Device Response Time With no DALI being received entering parameters will prompt you to enter the device response time menu for response R E S P O N S E S A D D 1 W A I T I N G F O R R E S P O N S E Using the up down keys to change the address setting if a response is received at an address the bl...

Страница 20: ...d with a load of short addressed level commands Block Repeat Data Pressing the Yes key toggles between on or off If set on when in advanced commands only new data will be stored into memory Display Find Sets the level the fixture will be lit to in discovery patch remove address etc range 0 to 100 Advanced Menus Pressing the Yes key toggles between on or off With Advanced Menus set to off some of l...

Страница 21: ...send twice s add grp all 00100000 RESET NONE 33 send twice s add grp all 00100001 STORE ACTUAL LEVEL IN DTR NONE 34 41 s add grp all 0010 RESERVED N A 42 send twice s add grp all 00101010 STORE DTR AS MAX LEVEL NONE 43 send twice s add grp all 00101011 STORE DTR AS MIN LEVEL NONE 44 send twice s add grp all 00101100 DTR AS SYSTEM FALIURE NONE 45 send twice s add grp all 00101101 DTR AS POWER ON LE...

Страница 22: ... grp all 10011001 QUERY DEVICE TYPE Byte returned 154 s add grp all 10011010 PHYSICAL MINIMUM LEVEL Byte returned 155 s add grp all 10011011 QUERY POWER FAILURE Yes No 156 159 s add grp all 100111 RESERVED N A 160 s add grp all 10100000 QUERY ACTUAL LEVEL Byte returned 161 s add grp all 10100001 QUERY MAXIMUM LEVEL Byte returned 162 s add grp all 10100010 QUERY MIMIMUM LEVEL Byte returned 163 s ad...

Страница 23: ...VICES 10101001 00000000 ADDRESS GRP B CAST 10101001 0AAAAAA1 WITHOUT S ADD 10101001 1111111 INITIALISE Commands 259 through 270 are only processed following this command NONE 259 send twice 10100111 00000000 RANDOMISE NONE 260 10101001 00000000 COMPARE Yes No 261 10101011 00000000 WITHDRAW NONE 262 10101101 00000000 RESERVED N A 263 10101111 00000000 RESERVED N A 264 10110001 SEARCH ADDRESS HIGH N...

Страница 24: ...key until D I S C O V E R P R O G R A M A L L y e s t o e n t e r o r m e n u 4 Press the Yes button and the message WILL ERASE ALL DATA will be displayed Press Yes again to start discovery 5 The XTBA DALI Watch will erase all data and discover the first device at the end of the search the device to be programmed will be lit to 50 and the display will go to S A D D R E S S 1 m e N u r e j e c t y ...

Страница 25: ...5 of 26 Product 03 2013 XTBA 1986 2013 Use the up down buttons to alter the level and the left right buttons to alter the address You should now have a working system 9 If it all worked retire to the bar if not blame the contractor ...

Страница 26: ...3 XTBA 1986 2013 35 Fernleigh Road London N21 3AN 0208 882 0100 0208 882 9326 email dmx xtba co uk www xtba co uk CE Declaration of conformity XTBA declares that the following equipment meets the requirements of the EMC Directive 89 366 EEC WEE FC2753ZS ...

Отзывы: