addressing. If it responds to Global Level then it is connected but not short
addressed.
Adjust Group Levels:
Pressing the Yes button will enter the function and the
display will change to: This allows you to alter all DALI levels of all 16 groups.
G R P :
1
2
3
4
T X %
0
0
0
0
The upper line shows the group number and the lower the level transmitted.
Next to the TX is a % symbol if the unit is set for percent or D if set for
decimal. Use the Left and Right buttons to scroll through the DALI groups.
The first group on the left is the group that you have command of. Pressing
the Up/Down buttons will alter the level of that group. So by using the
Left/Right Up Down you can control all 16 groups.
Set Up Devices Loop
Quick Set Up Devices
Advanced Set Up
Discover/Program All
Discover/Program New
Patch Devices
Remove Short Address
Set
Up Scenes
Check Fixtures
Quick Set Up
In order to set up DALI fixtures values need to be transferred to the data
transfer register before the set up command transfers the value to the relevant
device slot and all commands sent twice in less than 100ms. This would take
some speedy finger action so the XTBA DALI Watch deals with all of this for
you so you don’t need to bother.
Pressing the Yes button the display will change to:
S E T U P A T
S H O R T A D D R
Y e s t o e n t e r
o r m e n U
Pressing the Menu button again will loop through short address (S.ADD)
Group or broadcast (B.CAST). This allows all types of set up. If broadcast is
selected the XTBA DALI Watch will display ? SET UP ALL DEVICES? To
warn you that you are about do globally change all connected devices.
Pressing Yes will take you into set up display.
> S E T
M A X I M U M
L E V E L
A D D R E S S
-
0
@
0 %
With the arrow > on the upper left of the display the Up/Down buttons control
which command to be sent. Commands available are: Set Maximum Level,
Set Minimum Level, Set Failure Level, Set Power On Level, Fade Time, Fade
Rate.