© XTBA 1986 – 2013
Word Range is the number of DALI words being received
D A L I
W O R D R A N G E
L =
0
H =
6 3 N U M =
6 4
L = Lowest address received. H = Highest address received and NUM
= number of addresses
.
Frame Time C1 to C1 is the time between channel one being received again
e.g. the total frame length in seconds.
F R A M E
T I M E
C 1
t O C 1
1 . 7 0
s e c o n d S
Framing Errors is the number of incorrectly formatted DALI words – hopefully
none.
Input Voltage
The DALI buss power is monitored during the interbyte time to give the high
value and during a low bit to give the low value. The high value should be
between 9.5 to 22 volts and the low value should be between 0 and 6.5 volts.
D A L I
I N P U T
V O L T A G E
L O W
0 . 0 V
H I G H
1 5 . 1 V
Device Response Time
With no DALI being received entering parameters will prompt you to enter the
device response time, ‘menu for response’.
R E S P O N S E
@
S . A D D
1
W A I T I N G
F O R
R E S P O N S E
Using the up/down keys to change the address setting if a response is
received at an address the blue led will flash and the display will change to:
R E S P O N S E
@
S . A D D
1
1 0 . 6 m s
I N
R A N G E
The XTBA DALI Watch sends ‘query ballast’ to the address and monitors the
response time. If the response is started less than 6.4ms or greater than
21ms the display will show ERROR. If between 6.5ms and 20ms ‘IN RANGE’.
If no response found (e.g. no fixture found) the display will show ‘WAITING
FOR RESPONSE.’