XTBA DALI Watch Manual Page
17
of
26
Product # - 03/2013
© XTBA 1986 – 2013
Pressing the Yes button will send out the setting. e.g. load the DTR and
transfer it to the scene memory.
Check Fixtures
This function is a quick check if the fixtures defaults on systems where all the
defaults are supposed to be the same. On pressing the Yes button the display
will change to:
S . A D D
0
N A
And the address will begin to count up. If no address is found the display will
show ‘NA’. If found the display will show ‘OK’.
The XTBA DALI Watch scans the fixture list and looks for the first valid
address. It then records the Max Level, Min Level, Power On Level and
System Failure Levels and compares the values against any other available
fixtures. If it sees a difference the display might change to:
S . A D D
5
M A X
L E V E L
y e s
T o
c o n t i n u e
In this case address 5 has a different max level. Pressing the Yes button will
continue the search.
At the end of the search the display will change to:
8
D E V I C E S
F O U N D
f u n c t I o n
t o
e s c a p e
This will display the number of valid addresses found
So you can tell how many active devices are on the system and if they are set
up to the same defaults. If any differences are found you can use Quick Set
Up in broadcast to ensure they all have the same defaults.
Query Devices
Pressing Menu when Query Devices is displayed will take you into the main
display. This is quick method of finding settings at an address. Alternatively
you can use Advanced Set Up to do much the same thing but this groups the
common commands into a simple menu loop. See also YES/NO note in
advanced.
?
M A X
L E V
@
1
9 9 %
m e n u = l a s t
y e s = n e x t
The Up/Down keys can be used to alter the short address. The Menu and Yes
buttons will take you to the last/next query function. Functions as follows: