Operator Interface
153378
2–21
Minimum AC
Frequency Delay
Displays as:
Min Hz Delay:
This parameter sets the time delay
value, in AC cycles, for the “AC
Frequency Low” (0010) fault. If
the grid frequency remains below
the minimum AC frequency
setting (Min AC Freq) for the
duration of this delay period, the
fault is then triggered. The limits
of this parameter are restricted by
UL 1741 requirements.
59
AC cycles 10
300
10
AC Auto-Clear Delay
Displays as:
AutoClear
Delay:
This parameter sets the time delay
value, in seconds, for the Auto-
Clear feature corresponding with
the AC Voltage and Frequency
(0013, 0012, 0011, and 0010)
faults. The AC Voltage and
Frequency must remain within
their respective limits before an
Auto-Clear can occur. The limits
of this parameter are restricted by
UL 1741 requirements.
60
Seconds
300
300
10
Modbus Protocol ON
Displays as:
Modbus ON:
This parameter sets the protocol
used by the serial port (J1004) on
the CCU2. The serial protocol can
be set to either Modbus ON (1) or
to Modbus OFF (0) [Xantrex
protocol].
61
0=Off
1=On
1
1
0
Modbus Address
Displays as:
Modbus Address:
This parameter sets the address
used by the Modbus protocol.
62
N/A
N/A
N/A
Table 2-3
Write Menu Parameters
Parameter
Description
ID
Units
Default
Value
Maximum
Value
Minimum
Value
Содержание GT100-208
Страница 1: ...Xantrex GT100 Grid TiedPhotovoltaic Inverter Operation and Maintenance Manual GT100 208 GT100 480 ...
Страница 2: ......
Страница 3: ...Xantrex GT100 Grid Tied Photovoltaic Inverter Operation and Maintenance Manual ...
Страница 8: ...vi ...
Страница 15: ...Safety 153378 xiii Figure i AC Utility Terminals Figure ii DC Terminals TB1 N A TB2 B C TB5 PV GND TB3 TB4 ...
Страница 20: ...xviii ...
Страница 22: ...xx ...
Страница 24: ...xxii ...
Страница 46: ...1 22 ...
Страница 94: ...4 14 ...
Страница 108: ...B 2 ...
Страница 110: ...B 4 ...
Страница 117: ......