Specifications
A–2
153378
System Specifications
The GT100 has been designed for photovoltaic power systems, which operate
within the following specifications.
Environmental Specifications
CAUTION: Equipment Damage
Operation of the GT100 in a manner other than specified in this manual may cause
damage to the GT100 and other system components and will void the terms of
the warranty.
Table A-1
Environmental Specifications
Specification
Value
Dimensions
1861.8 mm H x 1702.0 mm W x 1171.0 mm D
(73.3 in. H x 67.0 in. W x 46.1 in. D)
Weight
1361 kg (3000 lbs)
Allowable Ambient Temperature
Operating
Storage
-15 °C to 50 °C Maximum (5 °F to 122 °F)
-40 °C to 50 °C Maximum (-40 °F to 122 °F)
Relative Humidity
to 95%, non-condensing
Elevation
2000 m (6600 ft)
Protection Class
NEMA 3R
Clearance (ventilation and
serviceability)
Top
Front
Sides
Rear
305 mm (12 in)
800 mm (31.5 in) (door clearance) plus local safety standards
0 mm (0 in)
0 mm (0 in)