Fault Code Descriptions
153378
4–7
XX30
Matrix Over Current H
This fault indicates that the GT100
has detected that the AC current on
one or more phases of the IGBT
matrix has exceeded the maximum
allowed value of 1400A
rms
.
The first two digits of the fault code
indicate the particular phase where
the over current occurred as follows:
• 0130 - Matrix over current in
phase A
• 0230 - Matrix over current in
phase B
• 0430 - Matrix over current in
phase C
If more than one phase faults
simultaneously, the two first digits
are added in hexadecimal form to
indicate an over current condition in
more than one phase, thus the error
code will contain the summation of
the faulted phases.
• P3 or P1002 on CCU2
is loose or
disconnected
• AC system wiring
short
0033
Ground Over
Current
S
This fault indicates that the GT100
has detected that the ground fault
current has exceeded the maximum
allowed value. This maximum
allowed value for ground fault
current is 4 Adc.
• P3 or P2 on CCU2 is
loose or disconnected
• Ground -to-AC or
DC-to-System wiring
short
• F4 is blown
• F4 fuse holder is open
Table 4-1
Fault Codes
Error
Code Fault
Source(s)
Fault Type
H=Hardware
S=Software
Fault Description
Possible Causes
Содержание GT100-208
Страница 1: ...Xantrex GT100 Grid TiedPhotovoltaic Inverter Operation and Maintenance Manual GT100 208 GT100 480 ...
Страница 2: ......
Страница 3: ...Xantrex GT100 Grid Tied Photovoltaic Inverter Operation and Maintenance Manual ...
Страница 8: ...vi ...
Страница 15: ...Safety 153378 xiii Figure i AC Utility Terminals Figure ii DC Terminals TB1 N A TB2 B C TB5 PV GND TB3 TB4 ...
Страница 20: ...xviii ...
Страница 22: ...xx ...
Страница 24: ...xxii ...
Страница 46: ...1 22 ...
Страница 94: ...4 14 ...
Страница 108: ...B 2 ...
Страница 110: ...B 4 ...
Страница 117: ......