Fault Code Descriptions
153378
4–5
Fault Code Descriptions
Table 4-1 provides a complete description of all the fault conditions that may
occur on the GT100. Default values are shown, but some limits are user-
adjustable.
Table 4-1
Fault Codes
Error
Code Fault
Source(s)
Fault Type
H=Hardware
S=Software
Fault Description
Possible Causes
0000
No Faults
N/A
N/A
N/A
0010
AC Frequency Low
S
This fault indicates that the Utility
grid frequency is below or fell below
the minimum allowed value of
59.3 Hz (default) for greater than 10
cycles. This fault is auto-clearing.
Once the Utility grid frequency has
recovered within the acceptable
operating range, the GT100
will
qualify the value and automatically
clear this fault and resume normal
operation after a delay period.
• Utility grid frequency
fell below the
allowable limit
0011
AC Frequency High
S
This fault indicates that the Utility
grid frequency is above or rose
above the maximum allowed value
of 60.5 Hz (default) for greater than
10 cycles. This fault is auto-clearing.
Once the Utility grid frequency has
recovered within the acceptable
operating range, the GT100
will
qualify the value and automatically
clear this fault and resume normal
operation after a delay period.
• Utility grid frequency
rose above the
allowable limit
0012
AC Voltage Low
S
This fault indicates that the utility
grid voltage is below or fell below
the minimum allowed value of 88%
of nominal Vac for greater than 2
seconds. This fault is auto-clearing.
Once the Utility grid voltage has
recovered within the acceptable
operating range, the GT100
will
qualify the value and automatically
clear this fault and resume normal
operation after a delay period.
• Utility grid voltage fell
below the allowable
limit
• Fuses - F4, F5, F6 on
the Inrush Current
Assembly PCB are
blown.
• P1001 on CCU2 is
loose or disconnected
Содержание GT100-208
Страница 1: ...Xantrex GT100 Grid TiedPhotovoltaic Inverter Operation and Maintenance Manual GT100 208 GT100 480 ...
Страница 2: ......
Страница 3: ...Xantrex GT100 Grid Tied Photovoltaic Inverter Operation and Maintenance Manual ...
Страница 8: ...vi ...
Страница 15: ...Safety 153378 xiii Figure i AC Utility Terminals Figure ii DC Terminals TB1 N A TB2 B C TB5 PV GND TB3 TB4 ...
Страница 20: ...xviii ...
Страница 22: ...xx ...
Страница 24: ...xxii ...
Страница 46: ...1 22 ...
Страница 94: ...4 14 ...
Страница 108: ...B 2 ...
Страница 110: ...B 4 ...
Страница 117: ......