Operation
2–18
153378
Minimum Grid
Frequency
Displays as:
Min AC Freq:
This parameter sets the trigger
point value for “AC frequency
low” (0010) fault. If the grid
frequency is below this
parameter’s value, the fault is
triggered. The lower limit of this
parameter is restricted by UL 1741
requirements.
35
Hertz
59.3
59.8
57
Peak Power Tracker
Reference Voltage
Displays as:
PPT V Ref:
This is the initial PV voltage the
inverter is going to try to keep as it
goes into on line mode. If the
power tracker is off, the inverter
will draw current from the PV
array to maintain this reference
voltage. If the power tracker is on,
this is the reference voltage from
which the inverter start exploring
voltages that produce more power.
37
Volts
400
600
300
PV Wakeup Voltage
Displays as:
PV V Start:
This is the trigger point that
transitions the inverter from PV
Sleep state to PV Wake Up state.
When the PV voltage reaches the
value of this parameter the
inverter transitions into PV Wake
Up mode.
38
Volts
440
600
300
Time Delay for PV
Wake up
Displays as:
PV T Start:
Time delay to transition from PV
wake up state to PV On-line state.
Once the inverter is in PV Wake
Up mode, it waits for the amount
of time determine by this
parameter before transitioning into
PV on-line mode. During this time
the inverter checks that the PV
voltage is no less than the PV
wake voltage, otherwise it goes
into PV Sleep mode.
39
Seconds
300
1200
0
Time delay for PV
Sleep Test
Displays as:
PV T Stop:
This is the amount of time the
inverter will be in Sleep Test mode
if the output power continues to be
below “PV P Stop”. The inverter
will exit Sleep Test mode towards
on-line mode is the power is over
“PV P Stop” or towards Shutdown
mode is the “PV T Stop” timer
expires.
40
Seconds
300
1200
0
Table 2-3
Write Menu Parameters
Parameter
Description
ID
Units
Default
Value
Maximum
Value
Minimum
Value
Содержание GT100-208
Страница 1: ...Xantrex GT100 Grid TiedPhotovoltaic Inverter Operation and Maintenance Manual GT100 208 GT100 480 ...
Страница 2: ......
Страница 3: ...Xantrex GT100 Grid Tied Photovoltaic Inverter Operation and Maintenance Manual ...
Страница 8: ...vi ...
Страница 15: ...Safety 153378 xiii Figure i AC Utility Terminals Figure ii DC Terminals TB1 N A TB2 B C TB5 PV GND TB3 TB4 ...
Страница 20: ...xviii ...
Страница 22: ...xx ...
Страница 24: ...xxii ...
Страница 46: ...1 22 ...
Страница 94: ...4 14 ...
Страница 108: ...B 2 ...
Страница 110: ...B 4 ...
Страница 117: ......