Preventative Maintenance
5–6
153378
found to be or are suspected to be unacceptable, contact your Xantrex Technology,
Inc. distributor for factory replacements or recommendations. Replacement of any
damaged wires will be necessary.
Verify all mechanical connections are sufficiently tightened. Verify all conduction
surfaces are clean and free of corrosion. Mechanical electrical connections may
loosen over time primarily due to thermal cycling during normal operation. As
electrical connections loosen, impedance will increase at the connection,
eventually leading to possible fire and component damage. It is critical to check
all electrical connections every six months. See termination torque specifications
for AC connections in Table A-5 on page A–5. See termination torque
specifications for DC connections in Table A-6 on page A–5.
Transformer and
Inductor Enclosure
Remove the access panel on the transformer and inductors and inspect for any
accumulated dirt and debris within the enclosure. Vacuum enclosure whenever
dust or dirt is present.