EGCP-2 Engine Generator Control Package
Manual 26174
94
Woodward
KVA Switch High
Sets level, which when exceeded, will cause the kVA relay output to de-
energize. Only applicable for units with the relay#12 function configured for
kVA Load Switch.
Summary of kVA load switch action:
If the relay 12 output is configured for kVA Load Switch action:
If the three-phase sum of the generator kVA is greater than the kVA Switch Low
set point and less than the kVA Switch High set point, the K12 relay output will
energize. Any other kVA levels relative to the Low and High switch set points will
cause the K12 relay output to de-energize.
Reactive Load Control
VAR/PF Mode
Disabled
Unit does not PF share, or control PF under any circumstances.
VAR Control
Unit PF shares in isolated bus load sharing mode.
Unit controls kVAR in Base Load and Process Control Modes.
PF Control
Unit PF shares in isolated bus load sharing mode.
Unit controls PF in Base Load and Process Control Modes.
VAR/PF Gain
Controls Gain Response of unit in VAR/PF control mode.
NOT active in PF sharing mode.
Voltage Ramp Time
Ramp time from 0 to ±100% voltage bias output.
Controls response of units in PF sharing modes.
Controls ramp time of voltage during synchronization.
Controls ramp time of voltage during manual voltage adjust.
VAR/PF Sharing Gain
Controls Gain Response of unit in VAR/PF Sharing Mode.
Not active in VAR/PF Control Mode.
VAR/PF Stability
Controls Stability Response of unit in VAR/PF control mode.
NOT active in PF sharing mode.
KVAR Reference
When kVAR control mode is selected, this references the amount of kVAR
the generator will produce while in Base Load or Process control modes.
Can be set for generate or absorb levels of kVAR.
kVAR levels limited by Rated kVAR of unit.