Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
75
Number of Poles
Range:
2—18
Determines Speed/Frequency Relationship.
Number of Poles = 120 * Hertz / rpm
Number
of Poles
60 Hertz
Generator
50 Hertz
Generator
2
3600 rpm
3000 rpm
4
1800 rpm
1500 rpm
6
1200 rpm
1000 rpm
8
900 rpm
750 rpm
10
720 rpm
600 rpm
12
600 rpm
500 rpm
14
514 rpm
428 rpm
16
450 rpm
375 rpm
18
400 rpm
333 rpm
Number of Teeth
Range:
16—500
Determines rpm Scaling.
Engine Speed Readouts/Alarms.
System Frequency
Range: 50 or 60 Hz
Used as a basis for generator waveform analysis.
Defines typical operating frequency of generator.
Rated Speed
Synchronous Speed Of Generator Set.
Used in Speed Calculation to determine “sample” period for MPU input.
Rated KW
Range:
1—30000
Rated kW of Generator
Typically 0.8 x rated kVA
Rated KVA
Range:
1—30000
Rated kVA of Generator
Rated KVAR
Range:
1—30000
Rated kVAR of Unit.
Typically 0.6 x Rated kVA.