Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
25
Figure 3-7 Notes:
1. For Multiple or Single Engine Applications
a. Loss of Mains (LOM)
b. Mains Parallel or No Parallel
c. Prime
Power
2. K1 and K2 relays
a. Not supplied by Woodward
b. Relays should be connected as Normally Open contacts
Bus PT
40
41
Mains/Bus PT Input
Mains PT
Disconnect
(Normally
Closed)
(D08)
Local Bus PT
Connect
(Normally
Open)
(D07)
23
24
VIS-146C
02-5-29
K2-B
A
B or N
K2-A
21
22
(+V)
EGCP-2
K2*
A
B or N
(B for Delta, N for Wye)
(B for Delta, N for Wye)
-
K2
SHOWN DE-ENERGIZED
-
K2
RELAY IS NOT
NOTES:
SUPPLIED BY WOODWARD
Prime Power
Applications
Figure 3-8. Utility/Local Bus Single PT Wiring for Delta and Wye Configuration for
Multiple or Single Engine Prime Power Applications
Figure 3-8 Notes:
1. Multiple Engine Application
a. Prime
Power
2. Single Engine Application
a. Prime
Power
3. Uses
Bus PT only
4. K2
relay
a. Not supplied by Woodward
b. Relay should be connected using the Normally Open contacts