Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
87
Engine Run Time
Hours of Run Time on Engine
Increments every run hour on System Status screen display.
Retained in non-volatile memory—Does not require power to retain its
value. The memory is updated every 4 hours of continuous operation, and
every time the engine is stopped.
MW Hours
MW Hours on Generator
Increments in 0.1 MWH on System Status screen display.
Retained in non-volatile memory, this memory is updated every 4 hours of
continuous operation, and every time the engine is stopped.
Overspeed
Set for overspeed limit of engine.
Typically set for 10% above Rated Speed of engine.
Overspeed Alarm
Alarm Set Point.
Typically configured to Hard Shutdown for safety.
When “Start Sequencing” is Disabled, the PT signal is used to calculate the
overspeed signal. No MPU is needed in this condition.
Woodward recommends that the Speed/Frequency Mismatch Alarm
be set the same as the Overspeed Alarm to protect against the loss
of the MPU signal.
Battery Volt High Limit
Sensed DC voltage supply to EGCP-2.
Can be used to detect faulty charging circuit.
Battery Voltage Low Limit
Used to detect weak battery/failed charger.
Automatically Disabled during engine cranking.
High Oil Pressure
Uses Engine mounted pressure sensor.
Active when generator is stable.
Display is selectable for psi (American) or Bar (Metric).
Low Oil Pressure Pre-Limit
Used to sense failure of lube oil system.
Start Sequencing ENABLED, Active at 90% of Rated Speed plus 5 seconds
or when Generator Breaker closes plus 5 seconds
Start Sequencing DISABLED, Active when Fuel Solenoid output energizes
plus 30 seconds or when Generator Breaker closes plus 5 seconds