Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
177
Recommended Wire Types:
Size Insulation
Type
Use
0.3 mm²/
22 AWG
600V
Multiple conductor,
unshielded
Discrete I/O
PT inputs
0.3 mm²/
22 AWG
300V
Two conductor, shielded
Speed Bias, Voltage
Bias, MPU, Oil and
Water Sensors
1.0 mm²/
16 AWG
600V
Four conductor stranded,
unshielded
CT inputs
0.3 mm²/
22 AWG
30V
Two conductor stranded,
twisted pair, shielded, 124
Ω
impedance
RS-485
RS-422 (TX and RX)