EGCP-2 Engine Generator Control Package
Manual 26174
88
Woodward
Low Oil Pressure
Used to sense failure of lube oil system.
Start Sequencing ENABLED, Active at 90% of Rated Speed plus 5 seconds
or when Generator Breaker closes plus 5 seconds.
Start Sequencing DISABLED, Active when Fuel Solenoid output energizes
plus 30 seconds or when Generator Breaker closes plus 5 seconds
High H2O Temperature Pre-Limit
Uses engine mounted temperature sensor
Active once Generator is stable.
Display is selectable for degrees F (American) or degrees C (Metric).
High H2O Temperature
Uses engine mounted temperature sensor.
Active once Generator is stable.
Display is selectable for degrees F (American) or degrees C (Metric).
Low H2O Temperature
Useful for detection of failed jacket water heater.
Always
active.
Synchronizer
Synchronizer Mode
Permissive
Acts as a synch check device.
EGCP-2 will not issue speed or voltage bias commands, but if
synchronization conditions are within spec (phase and voltage), control will
issue a breaker close command.
Check
Used for checking synchronizer prior to commissioning.
EGCP-2 control actively synchronizes generator by issuing speed and
voltage bias commands, but
does not issue breaker closure command
.
Run
Normal operating mode.
Actively synchronizes and
issues breaker closure command
.
EGCP-2 control MUST be in RUN to operate as a dead bus closing device.
In multiple unit systems EGCP-2 control MUST have AUTO input active to
enable breaker control.
Figure 4-26. Typical Circuit Using Permissive Function and Run for Auto/Manual
Synchronizing
5 2 G
B r e a k e r C lo s e
m a n u a l c lo s e
a u to /m a n
s w i tc h