Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
213
Item: Range:
Default:
As Set Value:
Note:
LO OIL PRESS
PRE-LMT
Min: 0.0.
Max: 120.0
2.0 Bar or PSI
LO OIL PRESS
PRE-ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
LO OIL PRESS
LMT
Min: 0.0
Max: 120.0
15.0 Bar or PSI
LO OIL PRESS
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Soft Shutdown
HI H20 TEMP
PRE-LMT
Min: 50.0
Max: 300.0
125.0 °C or °F
HI H20 TEMP
PRE-ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
HI H20 TEMP
Min: 50.0
Max: 300.0
212.0 °C or °F
HI H20 TEMP
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Soft Shutdown
LO H20 TEMP
Min: 0.0
Max: 200.0
20.0 °C or °F
LO H20 TEMP
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled