Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
215
Real Load Control Menu
Item: Range:
Default:
As Set Value:
Note:
LOAD CONTROL
MODE
Normal
Soft Transfer
Droop
Normal
LOAD CTRL GAIN Min: 0.001
Max: 100.0
0.01
LOADSHARE
GAIN
Min: 0.1
Max: 2.0
0.72
LOAD STABILITY
Min: 0.0
Max: 20.0
2.00
LOAD
DERIVATIVE
Min: 0.0
Max: 20.0
0.20
LOAD CTRL
FILTER
Min: 0.01
Max: 10.0
1.0 Hz
BASE LOAD
REFERENCE
Min: 0.0
Max: 30000.0
50.0 kW
UNLOAD TRIP
Min: –10.0
Max: 30000.0
10 kW
Must be set less than
Baseload Ref
LOAD DROOP
Min: 0.0
Max: 50.0
5.0%
LOAD TIME
Min: 1.0
Max: 7200.0
10 s
UNLOAD TIME
Min: 1.0
Max: 7200.0
10 s
RAISE LOAD
RATE
Min: 0.01
Max: 100.0
2.00%/s
LOWER LOAD
RATE
Min: 0.01
Max: 100.0
2.00%/s
KW LOAD HIGH
LIMIT
Min: 0.0
Max: 30000.0
30 kW
KW HIGH LIMIT
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Warning
KW LOAD LOW
LIMIT
Min: 0.0
Max: 30000.0
5.0 kW
KW LOW LIMIT
ALARM
Disabled
Warning
Visual Alarm
Audible Alarm
Disabled
kVA SWITCH
LOW
Min: 0
Max: 30000
10 kVA
kVA SWITCH
HIGH
Min: 0
Max: 30000
100 kVA