9
•
Voltage mode
o
The input line jumper pairs
–
approach
from the LED’s side
(upper two jumper
pins must be closed)
o
Galvanically divided and independent input lines
o
Make attention to the polarity when wiring!
The device on the photo is configured to contact input mode (e.g. for safety sensors)
(the jumpers are closed by pairs at lower 2-pins position)
Mode
Contact
Voltage
Not inverted
•
NO (Normal Open)
•
Inactive mode: contact opened
•
Active mode: contact closed
•
High active
•
Inactive mode: 0…1V
•
Active mode: 2
…24V
Inverted
•
NC (Normal Closed)
•
Inactive mode: contact closed
•
Active mode: contact opened
•
Low active
•
Inactive mode: 2
…24V
•
Active mode: 0…1V