11
◼
EOL resistor
For the detection of wire cut, you have use and connect a
10kΩ
resistor by parallel to
the sensor contact.
◼
Connecting the alarm line (ALARM line)
The alarm system can be connected to the
ALR
input through a wire pair, thus it will be able to
forward its alarm signals
–
in Contact ID format
–
to the remote dispatcher centre.
Connect the cable wire pair to the
ALR
title Alarm
line’s terminal block (by sliding the companion piece
and inserting the stripped wire pair, then fixing the
screws).
When activating the output, the
ALR LED
–
beside
the output - indicates the active (closed) position with the appropriate color/light - during the
operation.
◼
Installing the IO-expansion board (optional)
The
Easy2S
®
firmware can handle the
IO-expander
board
also
(extension for 6pcs plus of inputs,
and 3pcs outputs). Therefore for the IO-board further parameters are available in the device
fiwmrare and they are also configurable by the
EasyTerm
®
configuration tool.
◼
Connecting the power supply
The 8-24V power-supply voltage (typically 12V power
adapter, or 24V DC power supply) can be connected to the
PWR
input. When connecting the power cables, the
device will be immediately started to operating, when the
PWR
LED
will indicate it with the appropriate color/light.