Specification text (2)
A pinging function can be carried out by a single person as a "1-to-1 test" for the
planned connection of the fire dampers.
Field modules for fire dampers and smoke protection dampers supply them with 24 V DC
operating voltage. Field modules for external sensors and actuators can supply them with
24 V DC voltage. Alternatively, an on-site 24 V DC voltage can be connected via the mod-
ule for the sensors and actuators.
Requirement-based control of a ventilation and air conditioning system in accordance with
time settings, and thermal and material loads:
Sequence controls for implementation of requirement-based setpoint values for volume flow
and pressure controllers in accordance with thermal and material loads (presence detec-
tor, CO2 switch) and master-slave controls.
Calendar controls for implementation of requirement-based setpoint values for volume flow
and pressure controllers, adapted to the operating times of the building. Simple creation
of calendar entries using timetable assistant.
Release group controls for upgrading cold smoke safety and fire protection by integrat-
ing volume flow and pressure controllers into release groups together with volume fire
dampers and smoke protection dampers, and sensors and actuators using I/O modules. The
devices in a release group can be all the field modules under a subnet controller. The
field modules within the release group monitor each other using a "heart beat signal".
Simple parametrisation of release group control using a matrix. The alarm function for
volume flow and pressure controllers is adjustable.
Graphic analysis of any number of setpoint and actual values from volume flow and pres-
sure controllers. Permanent logging of data. Parameters which are available for factory
pre-order, are applied automatically by the volume flow and pressure controllers. Field
modules for electronic volume flow and pressure controllers supply them with 24 V DC
operating voltage. Field modules for external sensors and actuators can supply them with
24 V DC voltage. Alternatively, an on-site 24 V DC voltage can be connected via the mod-
ule for the sensors and actuators.
Accordingly, they must consist of:
Wildeboer-Net software for installation on the user's PC as
user interface for visualisation of the operating and diag-
nostics data collected in the field. For parametrisation and
control of connected modules.
........ pc. of WiNet-SW-01
deliver: ........
Manufacturer: WILDEBOER
install:
........ ........
Central operating unit with 15.6-inch multi-touch glass dis-
play for installation on the IP65 switch cabinet front panel.
Mains connection via plug-in power supply unit to 230 V AC.
Fully pre-installed with the operating system and with the
WiNet-SW-01 Wildeboer-Net software for data communication
with subnet controllers via Ethernet. For visualisation of
the operating and diagnostics data saved on the modules and
control of parametrisation of the field modules.
........ pc. of WiNet-ZB-01
deliver: ........
Manufacturer: WILDEBOER
install:
........ ........