Net
User Manual 7.1 (2019-04) 22
Subject to change
WiNet-GW-01 gateway
WiNet-GW-02 gateway
for BACnet, Modbus and OPC Server
DA 2.0
•
Housing 65 mm x B x 100 mm (L x B x H)
B = 31 mm for WiNet-GW-01, -02
B = 48 mm for WiNet-GW-03, -04, -05, -06
Protection class III, protection rating IP20
•
DIN mounting rail TS35 according to EN 50022
•
Supply voltage 12 – 24 V AC/DC
•
Current consumption max. 200 mA
•
Operating temperature range 0 – 45°C
•
Relative humidity 20 – 80% without condensation
•
Module permanently stores configuration, even in the
event of a power failure.
•
Galvanically isolated RS485 interface with plug-in
screw
terminal.
•
Development and automatic generation of the EDE file
required for BACnet using the Wildeboer-Net software.
⇒
see page 8
•
Types with corresponding data points
WiNet-GW-01:
200 Data points
WiNet-GW-02: 1100 Data points
WiNet-GW-03:
200 Data points
WiNet-GW-04: 1100 Data points
WiNet-GW-05:
200 Data points
WiNet-GW-06: 1100 Data points
An update to 2500 data points is possible.
71
72
73
74
75
3
1
4
1 2
1 2 3 4
1
ON
2 3
Power
LAN
RS485
DIP switch
LON
1 2 3 4
KNX
1 2 3 4
1 + KNX connection
2 + KNX connection
3 - KNX connection
4 - KNX connection
1 Shield: Shield
2 Shield: Shield
3 LON: LON2
4 LON: LON1
3
WiNet-GW-05 gateway
WiNet-GW-06 gateway
for BACnet, Modbus,
OPC Server DA
2.0 and KNX
1
3
5
1 +24: 24 V AC/DC supply voltage
2 GND: GND
RJ45 10/100 Mbit Ethernet
1+2: Bias voltage for RS485
ON: If few RS485 devices are connected
or no other RS485 device specifies a bias
voltage
3: 120 Ω terminating resistor
ON: If the gateway is connected to the end
of a RS485 chain.
WiNet-GW-03
WiNet-GW-04
WiNet-GW-05
WiNet-GW-06
1 B+:
non-inverted input
2 A-:
inverted input
3 AGND: GND
4 Shld: Shield connected to PE
Data cable: Twisted pair, 120 Ω,
shielded
4
1
5
2
4
2
2
Gateways
WiNet-GW-03 gateway
WiNet-GW-04 gateway
for BACnet, Modbus, OPC Server
DA 2.0 and LON
Wildeboer-Net
Products (7)