background image

Net

User Manual 7.1 (2019-04) 12

Subject to change

Wildeboer-Net

Functions (5)

Fire detection  

system coupler

Release group control  

⇒ 

see page 2 (MBO)

To ensure that the building is sealed off internally in case of fire, it is often necessary to close other fire dampers when 

one fire damper is released. Release groups are defined for this purpose.
Fire dampers can additionally be activated by smoke detectors in order to comply with the building code requirements 

for the cold smoke safety of ventilation and air conditioning systems. Depending on the requirement, this is performed 

either in a decentralised manner on the fire dampers and/or centrally using a fire detection system. Within Wildebo-

er-Net volume flow and pressure controllers can additionally contribute to cold smoke safety (VDI 6010) by carrying 

out a passive alarm function as passive devices in release groups. These controllers cannot release the group. The 

release of a group must always be acknowledged with the Wildeboer-Net software.
Release groups are parametrised by the Wildeboer-Net software and transferred to the field modules in the form of 

release group matrices. In the process, the field devices connected to the field modules can always be included as 

devices in one or multiple release groups.
The field modules monitor each other mutually within a release group. For this purpose each field module must receive 

what is referred to as a "heart beat signal" (sign of life) from every other field module within a certain time interval. If 

this "heart beat signal" is not received for a longer period, the devices in the affected group automatically assume their 

safe status. In the case of fire dampers this is the CLOSED position. The safe status of other field modules depends 

on the respective parametrisation. Possible causes for the missing signal include, for example, power failure on a 

field module or a bus interruption.
Release group controls in Wildeboer-Net are restricted to the field level of a subnet controller. Release groups can 

be connected universally for all subnet controllers using additional on-site fire detection system couplers or by inte-

grating fire detection panel modules or I/O modules. The use of FACP modules is recommended due to the existing 
line monitoring.  

⇒ 

see page 21

This way, it is possible to comply with the cold smoke safety requirements of MBO.

Example 3: 

Universal to all subnet controllers with fire detection system coupler

Example 2: 

Universal to all subnet controllers with FACP module

Motor module

FACP module

Release group 1

Release group 2

Fire detection 

system

Fire detection  

system coupler

FKKUE module

I/O module

Subnet controller 2

Subnet controller 1

Motor module

FACP module

Release group 1

Release group 2

FKKUE module

FACP module

Motor module

Motor module

Subnet controller 1

Motor module

FKKUE module

Release group 1

Motor module

Example 1: 

Single release group

Subnet controller 2

Subnet controller 1

Motor module

Motor module

Содержание BS2-BZ-01

Страница 1: ...Net User Manual 7 1 2019 04 1 The German original version of this document shall prevail Communication system Wildeboer Net Modules for volume flow pressure controller user s signalling units NEW...

Страница 2: ...s the use of fully maintenance free fire dampers The functional check of the fire dampers is the responsibility of the owner of the ventilation system Note The local inspection by a specialist inspect...

Страница 3: ...e functional checks are permanently stored and can be exported A graphic trend analysis of the results allow you to detect weaknesses in good time see page 2 MVV TB Energy efficiency Wildeboer Net imp...

Страница 4: ...3 Sub network 2 Cable length per sub network up to 3 200m Cable length in total per subnet controller 12 800m Cable length up to 100m Cable length up to 100m between modules Cable length up to 100m Ca...

Страница 5: ...can be forwarded via an OPC UA server The connected periphery is supplied with 24 V DC of power from the motor IO and volume flow and pressure controller modules Field modules and subnet controllers p...

Страница 6: ...to four subnets and for data exchange with the higher management level via Ethernet see page 16 Field level BS2 VR 01 volume flow and pressure controller module for connection of up to four elec troni...

Страница 7: ...If fire dampers are connected the fusible link can be pulled off or the test button on the motor can be actuated to trigger the desired fault message The fire dampers must be in the OPEN position for...

Страница 8: ...nt max 30 characters GIS code 1 Module VC 310 technology 375 01 M 431 102 K00 0120 2 Motor 1 VC 311 fire damper supply air 375 01 M 431 102 G053 0023 S 01 3 Motor 2 VC 311 fire damper exhaust air 375...

Страница 9: ...lled shut off of the fan If this is not possible and if there is a risk of damage to the duct network due to the fan running down and the fire dampers closing on site measures must be taken to prevent...

Страница 10: ...started functional checks the fan enabling function see page 9 using an optional I O module should definitely be used to shut off the fan Scheduled functional checks are monitored to make sure that t...

Страница 11: ...s been signalled via an input of the I O module to confirm that the fan has been shut off The mechanism is valid for non scheduled and scheduled manually started functional checks The fan has to be sh...

Страница 12: ...must receive what is referred to as a heart beat signal sign of life from every other field module within a certain time interval If this heart beat signal is not received for a longer period the devi...

Страница 13: ...editor can be used to read out and display the generated sequence controls Sequence controls can be created separately for each field module The status data from the respective field module and the st...

Страница 14: ...defined points in time or at fixed intervals For example motor modules or the FKKUE 03 control unit for FK90 fire damper for commercial kitchens can be used to close the connected fire and smoke prote...

Страница 15: ...s an example with a master slave function Graphic analysis The Wildeboer Net software also provides graphic analyses which allow you to detect trends simply They can be used for example to display res...

Страница 16: ...a gateway with higher level building control systems During commissioning the field modules connected to the subnets are detected and addressed automatically Four galvanically isolated CAN BUS connect...

Страница 17: ...the connected controllers from the volume flow and pressure controller module Existing VRE1 or VKE1 volume flow controllers can be connected via SM 01 interface modules Connected controllers are dete...

Страница 18: ...rs have to close when a particular one is closed and if fans have to be switched off All actuations and functions are remote controlled or controlled using the motor module s push buttons Fire dampers...

Страница 19: ...s Plug in screw terminals for the duct connection 3 1 M 24 V DC GND 1 2 3 5 6 7 8 Motor module BS2 MO 03 2 7 5 Motor connection using screw terminals 7 6 Limit switch connection using screw terminals...

Страница 20: ...s 24 V DC GND IN 8 1 2 3 4 5 6 7 8 9 10 IN 7 IN 6 IN 5 IN 4 IN 3 IN 2 IN 1 VDC GND werkseitige Br cken entfernen 1 2 3 4 5 6 7 8 9 10 Operating voltage 24 V DC SELV from the I O module Operating volta...

Страница 21: ...cables are monitored for faults Two floating outputs 2 30 V DC 10 A 2 A Connections with plug in screw terminals CAN CAN 7 3 inputs 7 4 outputs FACP module BS2 BZ 01 3 4 2 2 Remove the terminating res...

Страница 22: ...00 Data points WiNet GW 04 1100 Data points WiNet GW 05 200 Data points WiNet GW 06 1100 Data points An update to 2500 data points is possible 7 1 7 2 7 3 7 4 7 5 3 1 4 1 2 1 2 3 4 1 ON 2 3 Power LAN...

Страница 23: ...onnection of Wildeboer Net to the following open communication protocols Different protocols can also be operated simultaneously with a single gateway Data point definition see page 8 Information is e...

Страница 24: ...tware The OPC UAserver software facilitates the integration of Wildeboer Net into SCADAapplications SCADA supervisory control and data acquisition denotes a computer system in which technical processe...

Страница 25: ...arametrisation Our customer service department can provide supporting instructions on the operation of the software and the system for commissioning For example this includes instruction on generating...

Страница 26: ...0 KNX with 200 Data points WiNet GW 06 Gateway for BACnet Modbus OPC Server DA 2 0 KNX with1100 Data points see pages 22 23 WiNet OPC 01 OPC UA server software see page 24 Automation level BS2 SC 01 S...

Страница 27: ...collected separately for each field module and for each field device Additionally existing identification codes can be applied in accordance with the general identification system GIS Optionally the e...

Страница 28: ...ontroller The field modules within the release group monitor each other using a heart beat signal Simple parametrisation of release group control using a matrix The alarm function for volume flow and...

Страница 29: ...are developed and an EDE file is gen erated by the Wildeboer Net software pc of WiNet GW 03 deliver Manufacturer WILDEBOER install Gateway for the implementation of Wildeboer Net on BACnet IP Modbus...

Страница 30: ...rollers via RS485 or MP Bus Connection of the controllers using spring terminals Mains connection 230 V AC with standard Europlug and 1 5 m connecting line Galvanically isolated bus connections with p...

Страница 31: ...tored for faults Mains connection 230 V AC with stand ard Europlug and 1 5 m connecting line Galvanically iso lated bus connections with plug in screw terminals Manual operation using push buttons LED...

Страница 32: ...WEENER EMS Utrecht K LN Factory Administration Telephone 49 0 4951 950 0 Fax 49 0 4951 950 27120 E mail info wildeboer de Internet www wildeboer eu Utrecht office Telephone 31 30 767 0150 E mail info...

Отзывы: