background image

Net

User Manual 7.1 (2019-04) 10

Subject to change

Wildeboer-Net

Functions (3)

Functional checks  

⇒ 

see page 2 (MVV-TB)

The functional check is the only regular maintenance measure required for maintenance-free fire dampers. The damper 

blade has to be moved from the OPEN position into the CLOSED position, and then back into the OPEN position. 

This task is performed by the motor modules in Wildeboer-Net. 
The prerequisite for a remote-controlled functional check is that the motorised fire damper has been checked reliably 

to make sure that the CLOSED and OPEN positions are reached and this has been documented. The limit switches 

required for this purpose are included in the motors on the fire dampers. The running performance of the fire damper 

is recorded. The results of the functional check are stored reliably and permanently on the field modules, and in the 

Wildeboer-Net software after downloading.
The functional check can be carried out for all fire dampers simultaneously, but also for selected groups or individual 

fire dampers. This only ever takes a few minutes, regardless of the number of dampers. As a result, even on large 

systems the influence of the checks on operation are reduced to a minimum. This way, functional checks can be 

carried out problem-free at shorter intervals, thus increasing the reliability and availability of the system considerably.
Functional checks can be scheduled easily using a timetable. They are started automatically or manually at a defined 

deadline. For scheduled automatically started functional checks the fan enabling function 

(

⇒ 

see page 9), 

using an optional 

I/O module, should definitely be used to shut off the fan. Scheduled functional checks are monitored to make sure 

that they are carried out. Checks which are carried out with a delay, or not carried out at all, are marked accordingly 

in the logs.
Functional checks can also be started manually at any time. A manual shut-off of the fan can be parametrised for 

manually started functional checks. A functional check can be started locally using a motor module, regardless of the 

status of commissioning of the overall system. This way, it is possible to locally check that the fire damper is properly 

connected to the motor module and also check that the fire damper is fully functional, directly after installation. This 

makes it much easier to carry out commissioning of the overall system at a later time.
To assess the results of the functional check using the Wildeboer-Net software, the data has to be read out by the 

decentralised field modules. During the download, parametrised sequence controls, calendar controls and release 

groups are deactivated. On larger systems the download can take a few minutes. A table view which contains all 

dampers, and a graphic trend analysis (

⇒ 

see page 15

) for individual dampers are available for analysis purposes. This 

way, any required maintenance measures can be detected and arranged in good time. An export function to Excel is 

available for documentation purposes. 
That way, the building code requirements in MVV-TB for regular checking of the function of the fire dampers can be 

met from a central point.

Download

Permanent logging

on the modules

in the Wildeboer-Net 

software

Graphic analysis

Export

Содержание BS2-BZ-01

Страница 1: ...Net User Manual 7 1 2019 04 1 The German original version of this document shall prevail Communication system Wildeboer Net Modules for volume flow pressure controller user s signalling units NEW...

Страница 2: ...s the use of fully maintenance free fire dampers The functional check of the fire dampers is the responsibility of the owner of the ventilation system Note The local inspection by a specialist inspect...

Страница 3: ...e functional checks are permanently stored and can be exported A graphic trend analysis of the results allow you to detect weaknesses in good time see page 2 MVV TB Energy efficiency Wildeboer Net imp...

Страница 4: ...3 Sub network 2 Cable length per sub network up to 3 200m Cable length in total per subnet controller 12 800m Cable length up to 100m Cable length up to 100m between modules Cable length up to 100m Ca...

Страница 5: ...can be forwarded via an OPC UA server The connected periphery is supplied with 24 V DC of power from the motor IO and volume flow and pressure controller modules Field modules and subnet controllers p...

Страница 6: ...to four subnets and for data exchange with the higher management level via Ethernet see page 16 Field level BS2 VR 01 volume flow and pressure controller module for connection of up to four elec troni...

Страница 7: ...If fire dampers are connected the fusible link can be pulled off or the test button on the motor can be actuated to trigger the desired fault message The fire dampers must be in the OPEN position for...

Страница 8: ...nt max 30 characters GIS code 1 Module VC 310 technology 375 01 M 431 102 K00 0120 2 Motor 1 VC 311 fire damper supply air 375 01 M 431 102 G053 0023 S 01 3 Motor 2 VC 311 fire damper exhaust air 375...

Страница 9: ...lled shut off of the fan If this is not possible and if there is a risk of damage to the duct network due to the fan running down and the fire dampers closing on site measures must be taken to prevent...

Страница 10: ...started functional checks the fan enabling function see page 9 using an optional I O module should definitely be used to shut off the fan Scheduled functional checks are monitored to make sure that t...

Страница 11: ...s been signalled via an input of the I O module to confirm that the fan has been shut off The mechanism is valid for non scheduled and scheduled manually started functional checks The fan has to be sh...

Страница 12: ...must receive what is referred to as a heart beat signal sign of life from every other field module within a certain time interval If this heart beat signal is not received for a longer period the devi...

Страница 13: ...editor can be used to read out and display the generated sequence controls Sequence controls can be created separately for each field module The status data from the respective field module and the st...

Страница 14: ...defined points in time or at fixed intervals For example motor modules or the FKKUE 03 control unit for FK90 fire damper for commercial kitchens can be used to close the connected fire and smoke prote...

Страница 15: ...s an example with a master slave function Graphic analysis The Wildeboer Net software also provides graphic analyses which allow you to detect trends simply They can be used for example to display res...

Страница 16: ...a gateway with higher level building control systems During commissioning the field modules connected to the subnets are detected and addressed automatically Four galvanically isolated CAN BUS connect...

Страница 17: ...the connected controllers from the volume flow and pressure controller module Existing VRE1 or VKE1 volume flow controllers can be connected via SM 01 interface modules Connected controllers are dete...

Страница 18: ...rs have to close when a particular one is closed and if fans have to be switched off All actuations and functions are remote controlled or controlled using the motor module s push buttons Fire dampers...

Страница 19: ...s Plug in screw terminals for the duct connection 3 1 M 24 V DC GND 1 2 3 5 6 7 8 Motor module BS2 MO 03 2 7 5 Motor connection using screw terminals 7 6 Limit switch connection using screw terminals...

Страница 20: ...s 24 V DC GND IN 8 1 2 3 4 5 6 7 8 9 10 IN 7 IN 6 IN 5 IN 4 IN 3 IN 2 IN 1 VDC GND werkseitige Br cken entfernen 1 2 3 4 5 6 7 8 9 10 Operating voltage 24 V DC SELV from the I O module Operating volta...

Страница 21: ...cables are monitored for faults Two floating outputs 2 30 V DC 10 A 2 A Connections with plug in screw terminals CAN CAN 7 3 inputs 7 4 outputs FACP module BS2 BZ 01 3 4 2 2 Remove the terminating res...

Страница 22: ...00 Data points WiNet GW 04 1100 Data points WiNet GW 05 200 Data points WiNet GW 06 1100 Data points An update to 2500 data points is possible 7 1 7 2 7 3 7 4 7 5 3 1 4 1 2 1 2 3 4 1 ON 2 3 Power LAN...

Страница 23: ...onnection of Wildeboer Net to the following open communication protocols Different protocols can also be operated simultaneously with a single gateway Data point definition see page 8 Information is e...

Страница 24: ...tware The OPC UAserver software facilitates the integration of Wildeboer Net into SCADAapplications SCADA supervisory control and data acquisition denotes a computer system in which technical processe...

Страница 25: ...arametrisation Our customer service department can provide supporting instructions on the operation of the software and the system for commissioning For example this includes instruction on generating...

Страница 26: ...0 KNX with 200 Data points WiNet GW 06 Gateway for BACnet Modbus OPC Server DA 2 0 KNX with1100 Data points see pages 22 23 WiNet OPC 01 OPC UA server software see page 24 Automation level BS2 SC 01 S...

Страница 27: ...collected separately for each field module and for each field device Additionally existing identification codes can be applied in accordance with the general identification system GIS Optionally the e...

Страница 28: ...ontroller The field modules within the release group monitor each other using a heart beat signal Simple parametrisation of release group control using a matrix The alarm function for volume flow and...

Страница 29: ...are developed and an EDE file is gen erated by the Wildeboer Net software pc of WiNet GW 03 deliver Manufacturer WILDEBOER install Gateway for the implementation of Wildeboer Net on BACnet IP Modbus...

Страница 30: ...rollers via RS485 or MP Bus Connection of the controllers using spring terminals Mains connection 230 V AC with standard Europlug and 1 5 m connecting line Galvanically isolated bus connections with p...

Страница 31: ...tored for faults Mains connection 230 V AC with stand ard Europlug and 1 5 m connecting line Galvanically iso lated bus connections with plug in screw terminals Manual operation using push buttons LED...

Страница 32: ...WEENER EMS Utrecht K LN Factory Administration Telephone 49 0 4951 950 0 Fax 49 0 4951 950 27120 E mail info wildeboer de Internet www wildeboer eu Utrecht office Telephone 31 30 767 0150 E mail info...

Отзывы: