User Manual 7.1 (2019-04) 19
Subject to change
BS2-MO-02 Connection of fire dampers and/or smoke protection dampers to connection boxes
BS2-MO-03 Connection of the fire dampers and/or smoke protection dampers to a motor
module directly and to a connection box
CAN-out
CAN-in
bauseitige Leitung
8-adrig, 0,75 mm²
bis 100 m
Connection box AB-01 for fire dampers
with spring return actuator 24
V
DC
•
Plastic housing
140 mm x 110 mm x 67 mm (L x B x H)
protection class II, protection rating IP40.
•
Connection of dampers via the AMP
connectors of the motor connecting lines.
•
Plug-in screw terminals for the duct
connection.
3
1
M
+24 V DC
GND
1 2 3
5
6
7
8
Motor module
BS2-MO-03
2
75
Motor connection using
screw terminals
76
Limit switch connection
using screw terminals
3
1
2
3
1
M
+24 V DC
GND
77
Motor connection with
3-pin AMP connector
78
Limit switch connection
with 6-pin AMP connector
7
5
6 8
5
6 5 6
2
Motor module
BS2-MO-02
Connection box AB-01
Connection box
AB-01
Motor connecting line
approx. 0.75 m
CAN
CAN
CAN
CAN
on-site cables
8-wire 0.75 mm², up to 100 m
Motor connecting
line approx. 0.75 m
Motor connecting line
approx. 0.75 m
on-site cables
8-wire 0.75 mm², up to 100 m
Motor connect-
ing line
approx. 0.75 m
1 2 3
72
Sub-net-
work
Connection
Signal
12
CAN HIGH
2
CAN LOW
3
CAN shield
shielded 120
W
twisted pair
cable, 1 x 2 x 0.34
mm²,
max. 100 m between
modules
1
3
2
Wildeboer-Net