7. Description of program numbers
For an overview of the program numbers see appendix 1 “Overview of program
numbers”
7.1 Setting measuring inputs
7.1.1 Input signal
The digital indicator features two measuring inputs. Each measuring input can be set for
a different input signal.
PN Function
Parameter
0
Input signal, measuring input 1
Factory calibration
1 = DC 0 ... 10 V
2 = 0 ... 20 mA
3 = 4 ... 20 mA
Sensor calibration
4 = DC 0 ... 10 V
5 = 0 ... 20 mA
6 = 4 ... 20 mA
5
Input signal, measuring input 2
Parameters 1 ... 3 Used for standardised input signals. There must be no signal applied
to the measuring input. The corresponding display values can be
manually assigned.
→ For assigning display values, see chapter 7.1.2 “Start and end value”
Parameters 4 ... 6 Used for non-standardised input signals. The signal must be applied
to the measuring input and the corresponding display value manually
assigned.
→ For assigning display values, see chapter 7.1.2 “Start and end value”