35
WIKA operating instructions digital indicator, model DI35-D
EN
7.8.3 Switch points
PN
Function
Parameter
61
Switch point, switching output 1
-9999 ... 99999
71
Switch point, switching output 2
-9999 ... 99999
81
Switch point, switching output 3
-9999 ... 99999
91
Switch point, switching output 4
-9999 ... 99999
7.8.4 Switch behaviour
PN
Function
Parameter
62
Hysteresis, switching output 1
1 ... 99999
72
Hysteresis, switching output 2
82
Hysteresis, switching output 3
92
Hysteresis, switching output 4
63
Switching function, switching output 1
0 = Normally closed
1 = Normally open
73
Switching function, switching output 2
83
Switching function, switching output 3
93
Switching function, switching output 4
64
Switching delay, switching output 1
0 ... 10 seconds
74
Switching delay, switching output 2
84
Switching delay, switching output 3
94
Switching delay, switching output 4
65
Delay type, switching output 1
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switch-off delay
75
Delay type, switching output 2
85
Delay type, switching output 3
95
Delay type, switching output 4
7. Description of program numbers