26
WIKA operating instructions digital indicator, model DI35-D
EN
7. Description of program numbers
140553539.03 03/2020 EN/DE
7.2.2 Switching of measuring inputs
The switching of measuring inputs changes between the display values of the measur-
ing inputs and the display value of the arithmetic calculation. The display value of the
arithmetic calculation is only displayed when this has been configured.
The following methods are supported:
Method
Description
Static
A preset display value is shown for the duration of the trigger signal.
Triggered
With each trigger pulse, the measuring input is switched further (series
Ch1, Ch2, Ar).
Cyclic
The change is made cyclically over a preset time interval (series Ch1,
Ch2, Ar).
For the trigger signal, the multi-function button or the digital input can be used (see
chapter 7.7 “Setting special inputs”, PN 53/PN 54)
Before each change, the description of the measuring input is displayed.
■
Measuring input 1 = Ch1
■
Measuring input 2 = Ch2
■
Arithmetic calculation = Ar
PN
Function
Parameter
11
Switching of measuring inputs
0 = Key [▼] [▲] (triggered)
1 = Measuring input 1 (static)
2 = Measuring input 2 (static)
3 = Arithmetic function (static)
4 = Multi-function key (triggered)
5 = Cyclic (5 s)
6 = Cyclic (10 s)
7 = Cyclic (20 s)