56
WIKA operating instructions digital indicator, model DI35-D
EN
140553539.03 03/2020 EN/DE
PN Function
Parameter
Factory
setting
Authorisa-
tion level
59
Flashing display
0 = Deactivated
1 = at switch point 1
2 = at switch point 2
3 = at switch point 3
4 = at switch point 4
5 = at switch point 1 + 2
6 = at switch point 3 + 4
7 = at switch point 1 + 2 +
3 + 4
0
6
Switching output 1
60
Reference value
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
1
6
61
Switch point
-9999 ... 99999
1000
6
62
Hysteresis
1 ... 99999
1
6
63
Switching function
0 = Normally closed
1 = Normally open
1
6
64
Switching delay
0 ... 10.0 seconds
0.0
6
65
Delay type
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switch-
off delay
1
6
Switching output 2
70
Reference value
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
1
6
71
Switch point
-9999 ... 99999
1000
6
72
Hysteresis
1 ... 99999
1
6
73
Switching function
0 = Normally closed
1 = Normally open
1
6
74
Switching delay
0 ... 10.0 seconds
0.0
6
75
Delay type
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switch-
off delay
1
6
Appendix 1: Overview of program numbers