CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
98
Range
[Factory Setting]
Parameter
Unit
Description / Notes
When the Soft-Starter SSW-06 has been programmed to Current
Limit control, Torque Control or Current Ramp, this time acts as
maximum starting time, as a protection against locked rotor.
Figure 6.3
-
Acceleration ramp by Current Limit
NOTE!
The time set at P102 is not the exact motor acceleration time,
but the voltage ramp time or the maximum start time. The
motor acceleration time will depend on the motor and the load
characteristics.
Start
P102
0
P110
I(A)
I Limit
t(s)
Disable
Enable
Current Limit
Nominal Current
Maximum time
P103
99 to 60
Voltage Step
[ 100=Inactive ]
During Deceleration
1% Un of the
Motor
Used in applications with hydraulic pumps.
Set the nominal voltage (%Un), which will be applied to the motor
instantaneously when the Soft-Starter SSW-06 receives the ramp
deceleration command.
For more details about programming and use, refer to Pump Control
at P202.
NOTE!
To enable this function, you must set a deceleration ramp time.
P104
0 to 299
Deceleration
[ 0=Inactive ]
Ramp Time
1s
Used in hydraulic pump applications.
Enables and sets the time of the voltage decrement ramp.
For more details about programming and use, refer to Pump Control
at P202.
It can be used as Voltage Ramp control, Pump Control, Current
Limit and Current Ramp.
NOTE!
This function is used to lengthen the normal deceleration time
of a load and not to force a shorter time than that imposed by
the load.