CHAPTER 10 - TECHNICAL SPECIFICATIONS
186
10.3 POWER DATA
Supply
Capacity
Power voltage AC input (R/1L1, S/3L2, T/5L3)
Frequency
Maximum number of starts per hour
Starting Cycle
(220 to 575)Vac (-15% to +10%), or (187 to 632)Vac
(575 to 690)Vac (-15% to +10%) or (489 to 759)Vac
50 to 60Hz (± 10 %), or (45 to 66)Hz
10 (1 every 6 minutes) Models 10A to 820A.
5 (1 every 12 minutes) Models 950A to 1400A.
Standard motor connection
2 x InSSW during 60s
3 x InSSW during 30s
4.5 x (InSSW x 2/3) during 30s
Inside delta motor connection
2 x InSSW during 50s
3 x InSSW during 25s
4.5 x (InSSW x 2/3) during 25s
Maximum reverse peak voltage 1600V
III (UL508/EN61010)
Overvoltage Category
10.4 ELECTRONICS/PROGRAMMING DATA
(110 to 230)Vac (-15% to +10%), or (94 to 253)Vac
(50 to 60)Hz (± 10 %), or (45 to 66)Hz
280mA Maximum
Voltage Ramp;
Current Limit;
Pump Control;
Torque Control;
Current Control.
5 isolated digital inputs;
Minimum high level: 18Vdc;
Maximum low level: 3Vdc;
Maximum Voltage: 30Vdc;
Input Current: 11mA @ 24Vdc;
Programmable functions.
1 input for motor thermistor;
Actuation: 3k9
Ω
Release: 1k6
Ω
;
Minimum resistance: 100
Ω
;
PTCB referenced to the DGND through 249
Ω
resistor.
1 analog output, not isolated, (0 to +10)V, RL
≥
10k
Ω
(maximum load);
Resolution: 11bits;
Programmable functions.
1 analog output, not isolated,(0 to 20)mA/(4 to 20)mA, RL=500
Ω
/1%@10V;
Resolution: 11bits;
Programmable functions.
2 relays with NO-contacts, 240Vac, 1A, programmable functions;
1 relay with NO/NC-contact, 240Vac, 1A, programmable functions.
Supply
Control Voltage
Connector X1A (1,2)
Frequency
Consumption
Control Method
Inputs Digitals
Motor Thermistor
Input
Outputs Analogs
Relay
Thyristors (SCRs)